background image

7

2.3.  IN-PLANT TRANSPORT

CAUTION: 

The cabinet must not be moved by pulling the opened drawer! Pulling or sliding may only be carried out in 
the body housing!

M10

Steps for manoeuvring the cabinet:

• Open the drawer of the cabinet
• Connect the belts with steel angles or steel rings using a screw M10
• Screw the steel angles/rings into the threaded insert in the base of the 

cabinet

• Move the cabinet carefully using the belts

3. ERECTION • COMMISSIONING • FUNCTION

3.1.  COMMISSIONING

•  Before putting into operation for the first time, the user must carry out an examination of the safety storage 

cabinet for possible damage, such as defective or loose sealing elements, correct alignment and perfect func-
tioning of the door elements. 
Use the cabinet and accessories only if they are in an orderly condition.

3.2.  CONNECTION TO THE POWER SUPPLY

CAUTION 

The cabinet must be connected to the power supply at least 1 hour before storing items for the first time!

3.3.  ALIGNMENT OF THE CABINETS

After disabling the automatic door closing (see 4.4) and opening the drawer, the cabinet can be aligned 
using the integrated adjusting aids.

 

 

Summary of Contents for V Series

Page 1: ...unseren Garantieleistungen finden Sie unter www asecos com service leistungen For detailed information about our warranties please visit www asecos com service conditions EP V 31417_02 05 2020 BEDIENUNGSANLEITUNG Sicherheitsschränke V LINE USER MANUAL Safety storage cabinets V LINE GEBRUIKSAANWIJZING BrandveiligheidsopslagkastenV LINE NOTICE D UTILISATION Amoires de sécurite d aprés V LINE MANUAL ...

Page 2: ...V MOVE 90 V90 196 045 VDAC 0012 V90 196 081 VDAC 0012 V90 196 045 VDAC 0013 V90 196 081 VDAC 0013 ...

Page 3: ...k an uns Mit freundlichen Grüßen asecos GmbH YOUR PERSONAL DOCUMENTATION TO THE asecos SAFETY CABINET Dear Customer you have made a decisive investment in safety for your company by purchasing this asecos safety storage cabinet You now own an innovative product made of top quality materials guaranteeing the highest quality standards asecos safety storage cabinets have complete authorisation docume...

Page 4: ...tling of the transport packaging 6 2 3 In plant transport 7 3 ERECTION COMMISSIONING FUNCTION 7 3 1 Commissioning 7 3 2 Connection to the power supply 7 3 3 Alignment Of The Cabinets 7 3 4 locking of the cabinet 8 3 5 Unlocking of the cabinet 8 3 6 Automatic door closing system TSA 9 3 7 disable the automatic door closing system 9 4 SAFETY FUNCTIONS 10 4 1 Closing the drawer during blackout 10 4 2...

Page 5: ...rdous materials are to be collected immediately and removed Vessels containing aggressive chemicals acids alkalis are to be kept in special cabinets for acids and alkalis or on shelves for acids and alkalis as well as in cabinets with metal free interior equipmen Before storing such materials check that the cabinet s surface is resistant to the chemicals Before the initial commissioning the safety...

Page 6: ...f installation Inappropriate transport can lead to concealed damage to the fire protection insulation We can only guarantee the necessary quality if the cabinet is transported to the place of its use by our specially trained staff CAUTION The cabinet must not be moved by pulling the opened drawer Pulling or sliding may only be carried out in the body housing 2 1 TILTING THE CABINET 2 2 DISMANTLING...

Page 7: ...3 1 COMMISSIONING Before putting into operation for the first time the user must carry out an examination of the safety storage cabinet for possible damage such as defective or loose sealing elements correct alignment and perfect func tioning of the door elements Use the cabinet and accessories only if they are in an orderly condition 3 2 CONNECTION TO THE POWER SUPPLY CAUTION The cabinet must be ...

Page 8: ...DAC 2 2 1 2 3 4 5 6 V90 196 081 VDAC 2 3 1 2 3 4 5 6 NOTES to figures 4 and 5 Only one vertical drawer can be opened at a time while the other one remains closed 3 4 LOCKING OF THE CABINET 3 5 UNLOCKING OF THE CABINET ...

Page 9: ...9 3 6 AUTOMATIC DOOR CLOSING SYSTEM TSA 4 5 6 7 3 7 DISABLE THE AUTOMATIC DOOR CLOSING SYSTEM 3 3 sec 4 5 6 ATTENION In case of fire the automatic door closing is always ensured ...

Page 10: ...e note it only has power for one closing routine 15 sec 4 5 4 2 AUTOMATIC CLOSING IN THE EVENT OF FIRE 47 C 4 3 BLOCKING THE DRAWER WHILE OPENING Release blockage CAUTION If no direct user intervention occurs after the blockage the cabinet will give an acoustic and visual alarm after 20 seconds In that case please remove the blockade and follow the previous steps ...

Page 11: ...ING 10 cm 4 5 Release blockage 4 5 CAUTION If no direct user intervention occurs after the blockage the cabinet will give an acoustic and visual alarm after 20 seconds In that case please remove the blockade and follow the previous steps ...

Page 12: ... section front magnetic tape fixation points for screw M6 CAUTION Only the fixation points D shown in the drawing must be used Other fixation points or fixation types e g silicone are not permitted The magnetic tape mounted on the headboard serves as a support surface for the top cabinet and can be cut to size if required CAUTION The magnetic tape may only be attached to the rear head section 5 1 ...

Page 13: ... or at least 110 of the volume of the largest single container 2 whichever of these volumes is larger Use as a storage surface in case of cabinets with several storage levels 8 4 CAUTION Use as a storage surface is possible only in conjunction with a perfo rated metal plate insert Leaks Liquid in the sump is to be collected using suitable means 1 2 3 6 2 SHELVES HEIGHT ADJUSTABLE 6 3 SHELF GUARD R...

Page 14: ...e in relation to the total stored quan tity Applicable for all models Depending on the type class of the cabinet observe the respective valid national regulations 8 EARTHING An earth connection may be necessary depending on the customer specific use of the safety storage cabinet The decision regarding this is taken on the basis of a risk analysis by the customer Earthing when decanting Connection ...

Page 15: ...g a smoke tube Ventilation wheel for technical ventilation The ventilation wheel serves as an indicator for correct ventilation If the wheel turns the necessary 10 fold air recirculation rate is exceeded CAUTION In general these models can be operated without technical ventilation The direct environment of the cabinet can be an explosive zone in this case If the cabinet is to be operated without a...

Page 16: ...the drawers correct seating and condition of the fire protection seals 11 2 BATTERY CHECK Every six months after the maintenance check the battery should be checked by the user of the cabinet 3 15 sec 4 6 ATTENTION The rechargeable battery is considered a wearing part which has to be replaced every 3 years If this is not done in the course of an asecos service measure this must be done by the cust...

Page 17: ...17 ...

Page 18: ...ump in standby mode W 0 5 0 5 Max current consumption A 0 5 0 5 Nominal voltage V 85 265 85 265 Frequency Hz 50 60 50 60 Characteristics of each vertical drawer Maximum load vertical drawer kg 140 140 Max shelf load evenly distributed kg 50 00 50 00 Capacity bottom collecting sump litres 12 50 12 50 Volume massimo del contenitore litres 11 36 11 36 Max storage capacity litres 125 00 125 00 1 1 V90...

Page 19: ...VDAC 0013 1966 819 1448 Front view Side view Selectional view Shelf guard rail system Sump inliner PP Bottom collecting sump Perforated insert Shelf Anti slip rubber mat 399 88 230 860 294 88 Fresh air Exhaust air DN 75 Earthing link Top view ...

Page 20: ...asecos GmbH Abt Kundendienst Weiherfeldsiedlung 16 18 D 63584 Gründau Fax 49 60 51 92 20 10 www asecos com Ihr Fachhändler Your partner Uw partner Votre partenaire Su distribuidor su richiesta ...