13
6. INTERIOR FITTINGS
6.1. BOTTOM COLLECTING SUMP
1
2
According to EN 14470-1:
A spill containment sump must be
installed below the lowest storage level. The spill containment sump
must be able to hold a minimum volume of 10 % of all the containers
stored in the cabinet
[1]
or at least 110 % of the volume of the largest
single container
[2]
, whichever of these volumes is larger.
Use as a storage surface in case of cabinets with several storage levels:
8
4
CAUTION:
Use as a storage surface is possible only in conjunction with a perfo-
rated metal plate insert.
Leaks:
• Liquid in the sump is to be collected using suitable means.
1
2
3
6.2. SHELVES (HEIGHT-ADJUSTABLE)
6.3. SHELF GUARD RAIL SYSTEM
1
3
>3 sec
2
3
A
2×
4
4
B
2×
4
5
A2
B1
B2
A1
6
B1
7
≈8 cm
A1
8
Summary of Contents for V Series