Ascon Tecnologic - T82N- OPERATING INSTRUCTIONS - PAG. 5
5.3
Out2 Operating mode
The Output 2 operation can be programmed in
10 different
modes
with
F.o2t
parameter:
F.o2t
=
oF - Out2 Output disabled
F.o2t
=
1
-
Out2 works like Out1
Out2
output operates exactly like
Out1
output in order to
have a double output contact.
F.o2t
=
2
-
Out2 output works as an instant contact
(ON during count)
Out2
is activated during the counting phase and remains
active until the
Reset
command is received.
Reset
OUT1
f.o1t
=
1
Start
off
off
S.t1
OUT2
off
f.o2t
=
2
F.o2t
=
3
-
Out2 works as Out1 (with
s.t1
time)
but with an absolute
s.T3
time
This operating mode requires the setting of
S.t1
and
S.t3
Set times.
S.t3
has the same time range and cannot be
longer than
S.t1
.
Received the
Start
command, instrument starts counting
and operates on
Out2
output in the same mode it oper-
ates on
Out1
(as
f.o1t
).
If
f.o1t
=
1
,
4
,
5
,
Out2
operates with
ON delay
function
and
s.t3
of Set time, when instead
f.o1t
=
2
,
3
Out2
op-
erates with
Feed-through
function and
s.t3
of Set time.
Reset
OUT1
Start
off
f.o1t
=
1
,
f.o2t
=
3
S.t1
OUT2
off
off
off
S.t3
Reset
OUT1
Start
off
f.o1t
=
2
,
f.o2t
=
3
S.t1
OUT2
off
S.t3
Reset
Start
f.o1t
=
3
,
f.o2t
=
3
OUT1
off
off
S.t1
S.t1
S.t2
OUT2
off
off
S.t3
S.t3
Reset
Start
f.o1t
=
4
,
f.o2t
=
3
OUT1
off
S.t2
S.t1
OUT2
off
off
off
off
off
S.t3
S.t2
S.t1
S.t3
Reset
Start
f.o1t
=
5
,
f.o2t
=
3
OUT1
S.t2
S.t1
OUT2
off
off
off
off
S.t3
F.o2t
=
4
-
Out2 works as Out1 (with
s.t1
time)
but with a relative
s.t3
time in advance
This operating mode requires the setting of
S.t1
and
S.t3
Set times.
S.t3
has the same time range and cannot be
longer than
S.t1
.
Received the
Start
command, instrument starts counting
and operates on
Out2
output in the same mode it
operates on
Out1
(as
f.o1t
).
If
f.o1t
=
1
,
4
,
5
,
Out2
operates with
ON delay
function
and [
s.ti
-
s.t3
] of Set time, when instead
f.o1t
=
2
,
3
,
Out2
operates with
Feed-through
function and [
s.ti
-
s.t3
] of Set time.
Reset
Start
f.o1t
=
1
,
f.o2t
=
4
OUT1
S.t1
OUT2
off
off
off
off
S.t3
Reset
Start
f.o1t
=
2
,
f.o2t
=
4
OUT1
S.t1
OUT2
off
off
S.t3
Reset
Start
f.o1t
=
3
,
f.o2t
=
4
OUT1
off
off
S.t1
S.t1
S.t2
OUT2
off
off
S.t3
S.t3
Reset
Start
f.o1t
=
4
,
f.o2t
=
4
OUT1
off
off
S.t1
S.t2
OUT2
off
off
S.t3
S.t3
S.t1
S.t2
Reset
Start
f.o1t
=
5
,
f.o2t
=
4
OUT1
off
off
S.t1
S.t2
OUT2
off
off
S.t3
F.o2t
=
5
-
Activation at count end for the
S.t2
time
Out2
output thus configured can be used when an
end-of-count signal is required to activate an external
acoustic or luminous signalling device.
Reset
Start
f.o1t
=
2
,
f.o2t
=
5
OUT1
off
S.t1
OUT2
off
off
S.t2