Ascon tecnologic e31 Series Operating Instructions Manual Download Page 8

Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 8

5.8 

Alarm functions

The alarm conditions of the instrument are:

 

Probe errors 

E1

-E1

 and 

E2

-E2

;

 

Temperature alarms 

Hi

 and 

Lo

;

 

External alarm 

AL

;

 

Door open 

oP

.

All active alarms are pointed out on the instrument display 
lighting up the LED   and, if configured with parameter 

obu

also with the internal buzzer
Any active alarm condition is signaled lighting up the LED  , 
while the acknowledged alarm status is shown by flashing the  
LED  .
The buzzer (if present) can be configured to point out the alarms 
by programming parameter 

obu

 = 

1

 or 

3

 and always acts to 

signal the acknowlegeable alarms. This means that, when 
activated, it can be switched OFF by briefly pressing any key.

5.8.1 

Temperature alarms

The temperature alarm works according to 

Pr1

 or 

AU

 probes 

measurement, the type of alarm set in the parameter 

AAy

 the 

alarm thresholds set in parameters 

AHA

 (maximum alarm) 

and 

ALA

 (minimum alarm) and the relative differential 

AAd

.

Through parameter 

AAy

 it is possible to set the alarm thresh-

olds 

AHA

 and 

ALA

 as absolute or relative to the active Set 

Point, must be related to Pr1 or Au probes and if the message 

Hi

 (High alarm) and 

Lo

 (Low Alarm) are to be displayed at 

alarm intervention.
Depending on the desired alarm operating mode, parameter 

AAy

 can be set as:

1

 

Absolute alarms referred to probe Pr1, displays 

Hi

/

Lo

;

2

 

Relative Alarms referred to probe Pr1, displays 

Hi

/

Lo

;

3

 

Absolute alarms referred to probe Au, displays 

Hi

/

Lo

;

4

 

Relative Alarms referred to probe Au, displays 

Hi

/

Lo

;

5

 

Absolute alarm referred to probe Pr1, displays no labels;

6

 

Relative alarm referred to probe Pr1, displays no labels;

7

 

Absolute alarm referred to probe Au, displays no labels;

8

 

Relative alarm referred to probe Au, displays no labels.

Using some parameters it is also possible to delay the ena-
bling and the intervention of these alarms.
These parameters are:

APA

  Temperature alarm exclusion time on switching ON the 

instrument if the instrument is in alarm status when it 
is switched ON.  If the instrument is not in alarm status 
when it is switched on the time 

APA

 it is not considered.

AdA 

Temperature alarm exclusion time at the end of de-
frost cycle (and, if programmed, after the draining) or 
after a continuous cycle.

AAt

  Temperature alarms delay activation time.  Tempera-

ture alarms are enabled at the end of the exclusion 
times and are activated after the 

AAt

 time when the 

temperature measured by the probe exceeds or goes 
below the respective maximum and minimum alarm 
thresholds.  The alarm thresholds are those set at 
parameters 

AHA

 and 

ALA

 when the alarms are set as 

absolute (

AAy

 = 

1

3

5

7

).

Temp.

AHA

AAd

time

AL

ALA

AAd

off

off

off

ON

ON

Hi

Lo

Pr1

or they assume the values [

SP

 + 

AHA

] and [

SP

 + 

ALA

if the alarms are relative (

AAy

 = 

2

3

6

8

).

AHA

SP

ALA

off

off

off

ON

ON

Hi

Lo

time

AL

AAd

AAd

Temp.

Pr1

The maximum and minimum temperature alarms can be disa-
bled by setting the related parameters 

AHA

 and 

ALA

 = 

oF

.

The temperature alarms are signalled lighting up the alarm 
LED ( ) and, if configured, also with the buzzer

5.8.2 

External alarm from digital input

The instrument can signal an alarm external to the instrument 
using the digital input setting 

iFi

 = 

4

 or 

5

.  The instrument 

signals the alarm turning ON the alarm LED ( ) and display-
ing 

AL

 label alternated to the variable set with parameter 

Ids

.

Mode 

iFi

 = 

4

 operates no action on the control output, while 

iFi

 = 

5

 deactivates the control output at digital input inter-

vention.

5.8.3 

Open door alarm

The instrument can signal the open door alarm condition using 
the digital input setting 

iFi

 = 

1

2

 and 

3

.  As the Digital input is 

activated, the instrument signals that the door is open showing 
on the display the 

oP

 label alternated to the variable set with 

parameter 

ids

.

After the delay set with parameter 

AoA

 the instrument 

signals the Open Door alarm with the configured devices 
(buzzer and/or Output), lighting up the LED   while showing 
the 

oP

 label.  At the open door alarm intervention are also 

re-activated the inhibited outputs (compressor).

5.9 

Function of keys 

/  and 

/Aux

Two of the instrument keys, in addition to their normal func-
tions, can be configured to operate other commands.  
The 

/

 

key function can be defined using the 

tUF

 param-

eter while the 

/

Aux

 key via parameter 

TFb

.  Both param-

eters have the same possibilities and can be configured to 
perform the following functions:

oF

 The key carries out no function;

1. 

Do not use;

2. 

Pressing the key for at least 1 s, you can sequentially 
select a 

normal

 or 

eco

 operating mode (

SP

/

SPE

).  

A selection has been made the display shows for about 
1 s the active set point code (

SP

 or 

SPE

);

3. 

Pressing the key for at least 1 s is possible to switch the 
instrument from 

ON

 to 

Stand-by

 state and vice-versa;

4. 

Do not use.

Summary of Contents for e31 Series

Page 1: ...ypically used in cooling ap plications with ON OFF temperature control and defrost control with intervals time by stopping compressor The instrument has 1 relay output and 2 NTC temperature probes inp...

Page 2: ...PROGRAMMING 2 1 Fast Set point programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it...

Page 3: ...is protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The...

Page 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Page 5: ...ternal Buzzer SPST NO NO NO C SPDT NO NO NC C 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different condi tions ON Means that the controller uses the control function...

Page 6: ...The digital input function is defined using the iFi parameter and the action is delayed for the time programmed with pa rameter iti The iFi parameter can be configured for the following functions 0 D...

Page 7: ...n All these functions are disabled if the relative parameters are set to OFF oF 5 7 Defrost control The automatic defrost control is made with the stopping compressor method it occurs by interval time...

Page 8: ...rms delay activation time Tempera ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the re...

Page 9: ...ent are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please...

Page 10: ...Do not use HC Do not use C3 Do not use C 21 ddL Display Lock during defrost oF Not active on Active at last measure Lb Active with label dEF during defrost and PdF at defrost oF 22 dcd Defrost activat...

Page 11: ...scon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characte...

Page 12: ...2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Relay output SPST NO 30A AC1 resistive load R Relay output SPST NO 16A AC1 resist...

Reviews: