Ascon tecnologic e31 Series Operating Instructions Manual Download Page 4

Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 4

3.  USAGE WARNINGS

3.1 

Admitted use

D

D

The instrument has been projected and manufactured 
as a measuring and control device to be used accord-
ing to EN60730-1 at altitudes operation below 2000 m.  

Using the instrument for applications not expressly permitted 
by the above mentioned rule must adopt all the necessary 
protective measures.
The instrument 

MUST NOT BE USED

 in dangerous environ-

ments (flammable or explosive) without adequate protections.
The instrument used with NTC 103AT11 probe (identifiable 
by the printed code “103AT-11” visible on the sensor part) 
is compliant with standard EN 13485 (“Thermometers for 
measuring the air and product temperature for the transport, 
storage and distribution of chilled, frozen, deep-frozen/quick-
frozen food and ice cream”) with the following classification: 
[EN13485 air, S, A, 2, -50°C +90°C]
Remember that the end user must periodically check and veri-
fy the thermometers in compliance with standard EN 13486.
The installer must ensure that the EMC rules are respected, 
also after the instrument installation, if necessary using 
proper filters.

4.  INSTALLATION WARNINGS

4.1 

Mechanical mounting

The instrument, in case 78 x 35 mm, is designed for flush-
in panel mounting.  Make a 71 x 29 mm hole and insert the 
instrument, fixing it with the provided special brackets.
In order to obtain the declared front protection degree, mount 
the gasket and use the screw type bracket (both optional).
Avoid placing the instrument in environments with very high 
humidity levels or dirt that may create condensation or intro-
duction of conductive substances into the instrument
Ensure adequate ventilation to the instrument and avoid 
installation in containers that house devices which may 
overheat or which may cause the instrument to function at a 
higher temperature than the one permitted and declared.
Connect the instrument as far away as possible from sources 
of electromagnetic disturbances such as motors, power re-
lays, relays, solenoid valves, etc..

4.2 

Dimensions [mm]

4.2.1 

Mechanical dimensions

P

U

e31

Aux

35

28

12.2

14.5

8

6

64

78

4.2.2 

Panel cut-out

29

+0.6

71

+0.6

 mm

RECOMMENDED

PANEL CUTOUT

min.

 12 mm

min. 15 mm

4.2.3 

Mounting brackets

P

anel + Gask

et max.

 12 mm (#1)

max.

 29 mm (#2)

“Butterfly” type

brackets (#1)

Screw type

bracket (#2)

34

43

86

Summary of Contents for e31 Series

Page 1: ...ypically used in cooling ap plications with ON OFF temperature control and defrost control with intervals time by stopping compressor The instrument has 1 relay output and 2 NTC temperature probes inp...

Page 2: ...PROGRAMMING 2 1 Fast Set point programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it...

Page 3: ...is protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The...

Page 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Page 5: ...ternal Buzzer SPST NO NO NO C SPDT NO NO NC C 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different condi tions ON Means that the controller uses the control function...

Page 6: ...The digital input function is defined using the iFi parameter and the action is delayed for the time programmed with pa rameter iti The iFi parameter can be configured for the following functions 0 D...

Page 7: ...n All these functions are disabled if the relative parameters are set to OFF oF 5 7 Defrost control The automatic defrost control is made with the stopping compressor method it occurs by interval time...

Page 8: ...rms delay activation time Tempera ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the re...

Page 9: ...ent are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please...

Page 10: ...Do not use HC Do not use C3 Do not use C 21 ddL Display Lock during defrost oF Not active on Active at last measure Lb Active with label dEF during defrost and PdF at defrost oF 22 dcd Defrost activat...

Page 11: ...scon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characte...

Page 12: ...2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Relay output SPST NO 30A AC1 resistive load R Relay output SPST NO 16A AC1 resist...