Ascon Tecnologic - e31- - OPERATING INSTRUCTIONS - PAG. 7

ment so that that the output continues to work in cycles 
according to the times programmed with parameter 

rt1

 

(activation time) and 

rt2

 (deactivation time).

If an error occurs on the probe the instrument activates the 
output for the time 

rt1

, then deactivates it for the time 

rt2

 

and so on whilst the error remains.
Programming 

rt1

 = 

oF

 the output in probe error condition 

remains switched off.
Programming instead 

rt1

 to any value and 

rt2

 = 

oF

 the 

output in probe error condition remains switched ON.
Remember that the temperature regulation function can be 
conditioned by the 

Compressor Protections

Delay at power 

ON

 and 

Defrost functions

.

5.6 

Compressor protection function and 
power-on delay

The “

Compressor Protection

” function aims to avoid repeated 

compressor start-ups controlled by the instrument in cooling 
applications or otherwise can be used to add a timed control 
on the actuator control output.
This function foresees 3 time controls on the switching ON of 
the output associated with the temperature control request.  
The protection consists of preventing the output being 
switched ON during the times set with parameters 

PP1

pP2

 

and 

PP3

 and therefore that any activation occurs only after 

all times are elapsed.

1. 

First control (parameter 

PP1

) foresees a delay to output 

activation (switching-ON delay).

SP

time

off

off

off

off

ON

rd

PP1

PP1

PP1

PP1

OUT (ot)

Temp.

Pr1

ON

ON

2. 

Second control (parameter 

PP2

) foresees an inhibition to 

the activation of the output by a time delay that starts when 
the output is turning OFF (delay after switching-OFF).

SP

off

off

off

ON

rd

PP2

PP2

PP2

PP2

Temp.

Pr1

time

OUT (ot)

ON

ON

3. 

Third control (parameter 

PP3

) foresees an inhibition to 

the activation of the output by a time delay that starts 
when the output was turned ON last time (delay between 
two switching-ON).

SP

off

off

off

ON

rd

PP3

PP3

PP3

time

OUT (ot)

PP3

Temp.

Pr1

ON

ON

During the output inhibition the LED 

OUT

 (Cool

 

 or Heat

 

blinks.  It is also possible to prevent activation of the output 
after the instrument is turned ON, for the time set in the 
parameter 

Pod

.

During the power ON delay phase, the display shows the 
indication 

od

, alternated with the normal visualization.

All these functions are disabled if the relative parameters are 
set to 

OFF

 (

oF

).

5.7 

Defrost control

The automatic defrost control is made with the 

stopping 

compressor

 method; it occurs by interval times or after a 

certain time of continuous compressor functionning.
The automatic defrost function is activated when at parameter 

ddi

 is set the defrost interval time between 2 defrost cycles.

The first defrost after power on can be set by parameter 

dSd

.

This allows to perform the first defrost to a different interval 
from 

ddi

 time.

When the instrument must perform a defrost cycle at all power 
ON, set parameter 

dSd

 = 

oF

.

If all defrost cycles must be performed after the same inter-
val time, program 

dSd

 = 

ddi

.

Automatic defrost function is totally disabled when 

ddi

 = 

oF

 

(including the first, regardless the time set at 

dSd

 parameter).

The instrument provides to switch OFF the output for the 

ddE

 period of time every time expires the 

ddi

 time (or 

dSd

 

in case of first defrost after power ON).
Moreover, the instrument starts a defrost cycle when the 
compressor is activated continuously for the time 

dcd

.

This function is used as the continuous operation of the com-
pressor for a long period is normally a symptom of a low heat 
exchange typically caused by the frost on the evaporator.
By setting 

dcd

 = 

oF

 the function is disabled.

5.7.1 

Manual defrost

To start a manual defrosting cycle, press the key 

/  when 

it is not in programming mode and keep it pressed for about 
5 s after which, if the conditions are correct, the LED   will 
light up and the instrument performs out a defrosting cycle.
To stop a defrosting cycle, press the key 

/  during the 

defrost and keep it pressed for about 5 seconds.

5.7.2 

Display lock during Defrost

Through parameters 

ddL

 and 

AdA

 it is possible to define the 

display behaviour during defrost.  The 

ddl

 parameter can as-

sume the following values.

on 

The 

ddL

 parameter locks the display at the last tem-

perature reading during all the defrost cycle until, at 
the end of defrost, the temperature has not reached 
the lock value or the value [

SP

 + 

rd

] or is elapsed the 

time set at parameter 

AdA

Lb 

Shows the label 

dEF

 during the defrost cycle and 

PdF

 

after the defrost until, at the end of defrost, the tem-
perature has not reached the lock value or the value 
[

SP

 + 

rd

] or is elapsed the time set on parameter 

AdA

oF 

The display continues showing the temperature meas-
ured by the 

Pr1

 probe during the defrost cycle.

Summary of Contents for e31 Series

Page 1: ...ypically used in cooling ap plications with ON OFF temperature control and defrost control with intervals time by stopping compressor The instrument has 1 relay output and 2 NTC temperature probes inp...

Page 2: ...PROGRAMMING 2 1 Fast Set point programming The normal mode to program the setpoint is done by mo mentarily pressing the key the display shows SP or SPE alternated to the programmed value To change it...

Page 3: ...is protected If the dp LED is steady ON the parameter is programmable without password is unprotected To change the parameter visibility press the key and keeping it pressed also press the button The...

Page 4: ...d also after the instrument installation if necessary using proper filters 4 INSTALLATION WARNINGS 4 1 Mechanical mounting The instrument in case 78 x 35 mm is designed for flush in panel mounting Mak...

Page 5: ...ternal Buzzer SPST NO NO NO C SPDT NO NO NC C 5 FUNCTIONS 5 1 ON Stand by function Once powered the instrument can assume 2 different condi tions ON Means that the controller uses the control function...

Page 6: ...The digital input function is defined using the iFi parameter and the action is delayed for the time programmed with pa rameter iti The iFi parameter can be configured for the following functions 0 D...

Page 7: ...n All these functions are disabled if the relative parameters are set to OFF oF 5 7 Defrost control The automatic defrost control is made with the stopping compressor method it occurs by interval time...

Page 8: ...rms delay activation time Tempera ture alarms are enabled at the end of the exclusion times and are activated after the AAt time when the temperature measured by the probe exceeds or goes below the re...

Page 9: ...ent are being supplied directly or through the key AC supply Supply adapter 12 VDC Power supply Enter PWS 12 V A B C TTL USB to PC USB Enter PWS 12 V A B C TTL USB to PC USB For additional info please...

Page 10: ...Do not use HC Do not use C3 Do not use C 21 ddL Display Lock during defrost oF Not active on Active at last measure Lb Active with label dEF during defrost and PdF at defrost oF 22 dcd Defrost activat...

Page 11: ...scon Tecnologic with a detailed description of the faults found without any fees or charge for Ascon Tecnologic except in the event of alternative agreements 10 TECHNICAL DATA 10 1 Electrical characte...

Page 12: ...2 50 C 90 C with probe NTC 103AT11 11 HOW TO ORDER a POWER SUPPLY D 230 VAC C 115 VAC F 12 VAC VDC b OUTPUT 1 OUT 1 H Relay output SPST NO 30A AC1 resistive load R Relay output SPST NO 16A AC1 resist...

Reviews: