- sigmaPAC CU-02 -
User manual
18
3-2-12 Modbus TCP/IP Setup
Selecting item 3 on the Main Menu you will arrive at the following menu:
Figure 3.14 - Modbus TCP/IP Setup Menu
Messages per Cycle:
By the first item the user can insert the number of messages processed dur-
ing each cycle. The inserted value must be comprised between 1 and 50.
Broken Connection Timeout (s):
By the second item you can set the inactivity timeout of a TCP/IP con-
nection (in seconds). The inserted value must be comprised between
10 and 5400. To verify the connection state after a long period of inactiv-
ity, the TCP/IP “keepalive” protocol is used. The protocol performs in
sequence the following steps:
1.
At each received messages the timeout is zeroed;
2.
In the case that the programmed timeout is reached, a “probe”
message is sent in order to verify if the connection is still active;
3.
If an answer to the “probe” is received, then the timeout is zeroed.
4.
In case of no answer, the “probe” will be sent again three times,
every 10 seconds.
5.
After the fourth “probe” has got no answer the connection will be
closed.
Secure Address Setup:
Selecting this item a new window will appear displaying the menu
called “Secure Address Protocol”(see next);
Exit:
exit this menu and return to the previous menu.
MODBUS TCP/IP SETUP
1. Messages per cycle: 10
2. Broken connection timeout(s): 10
3. Secure Address Setup
4. Priority Address Setup
5. Exit
Enter Selection:
Ascon S.p.a.
SigmaPAC Control Unit CU-02
Device configuration