background image

4

Customer Care Center, 1-800-898-1879, www.askona.com

Connecting the exhaust duct to 
the left or right side outlet

To connect the exhaust duct to the left or 
right side outlet, follow the steps below:
1.  Using a fl athead screw-driver, turn the 

exhaust outlet cover you plan to use to the 
right or left to align the tabs holding the 
cover in place.

2.  Remove the exhaust outlet cover.
3.  Remove the stub pipe from the rear 

exhaust outlet and place it in the outlet you 
plan to use.

4.  Push the duct onto the stub pipe and 

secure it with a clamp.

5.  With the duct attached, insert the stub 

pipe into the hole. It should snap into place.

6.  After you push the dryer into place, check 

for kinks in the duct.

7.  Use the exhaust outlet cover you removed 

from the to cover the rear exhaust outlet.

WARNING!

•  To reduce the risk of fi re, this appliance 

must be exhausted OUTDOORS or the 
equivalent. Never cover the end of the dryer 
stub or exhaust duct with anything to catch 
lint, except for UL approved vent basket.

Connecting to a ventilation duct

You will need a UL-CSA-approved, 4-inch 
ridged metal exhaust duct. If a fl exible duct 
is used, it must comply with the Outline for 
Clothes Dryer Transition Duct. Subject 2158A 
and maximum length of 2.4 m (8 feet).

NOTE!

•  The more bends and the longer the 

duct, the less air will circulate through 
the machine, which will impede drying 
performance. We recommend that you cut 
off any excess exhaust duct and run the duct 
with as few bends as possible. And make any 
necessary bends as gentle as possible.

NOTE!

•  Maximum duct length of 60 feet. A 

maximum of 4 elbows may be used, but 4 
feet of duct must subtracted from the total 
vent length for every 90° elbow used.

NOTE!

•  When installing in warm climates (77° F and 

above) with high humidity levels, do not 
route the air exhaust duct upwards.

subtract 4 feet for 
every 90°elbow

Examples of 
installations

To connect the exhaust duct to a 
ventilation outlet, follow the steps below:

1.  Connect the exhaust duct to a ventilation 

exhaust fi tting or to a discharge through the 
wall.

2.  Secure the duct joint to the outlet stub on 

the machine.

3.  Run the duct with as few bends as possible 

to the point of discharge.

Ventilation grill (not supplied with machine)

WARNING!

•  This appliance shall not be exhausted into 

a chimney, a wall, a ceiling, an attic, a crawl 
space or a concealed space of a building. 
Only a rigid or fl exible metal duct shall be 
used for exhausting. Only a metal ventilation 
grill shall be used. If the duct is taken to a 
wall outlet, a ventilation grill shall be fi tted 
to prevent reverse fl ow of cold air. Fit the 
ventilation grill to the outside of the wall.

NOTE!

Avoid:
•  very long exhausting systems
•  too many corners
• tight corners
These reduce effi  ciency and increase time and 
energy consumption.

Electrical installation

WARNING!

•  The receptacle on the rear of the machine 

is designed to accommodate ASKO washers 
ONLY (rated 208–240 V.) To use this 
receptacle, you must use the ready-fi tted 
plug supplied with the washing machine or 
an equivalent.
ASKO washers rated 208–240 V have two 
internal fuses of 15 A each.
The machine should only be connected to a 
grounded wall socket.

WARNING!

•  This appliance must be properly grounded. 

Refer to the “Important Safety Instructions” 
for grounding instructions.
The power supply cord must be grounded. 
If the machine is to be used in a wet area, 
the supply must be protected by a residual 
current device.
Connection to a permanently wired supply 
point must be made only by a qualifi ed 
electrician. As supplied: Single-phase, 230 
V, 60 Hz, 3000W heater rating 30 A circuit 
required - only a power-supply cord kit 
rated 230 V min, 30 A, and marked for use 
with clothes dryers shall be used.

NOTE!

Do not connect the machine to the mains 
electricity supply by an extension lead.

Remove cover to 
access teminal box. 
(Requires- Torx 
screwdriver.)

Reviews: