4
Customer Care Center, 1-800-898-1879, www.askona.com
Connecting the exhaust duct to
the left or right side outlet
To connect the exhaust duct to the left or
right side outlet, follow the steps below:
1. Using a fl athead screw-driver, turn the
exhaust outlet cover you plan to use to the
right or left to align the tabs holding the
cover in place.
2. Remove the exhaust outlet cover.
3. Remove the stub pipe from the rear
exhaust outlet and place it in the outlet you
plan to use.
4. Push the duct onto the stub pipe and
secure it with a clamp.
5. With the duct attached, insert the stub
pipe into the hole. It should snap into place.
6. After you push the dryer into place, check
for kinks in the duct.
7. Use the exhaust outlet cover you removed
from the to cover the rear exhaust outlet.
WARNING!
• To reduce the risk of fi re, this appliance
must be exhausted OUTDOORS or the
equivalent. Never cover the end of the dryer
stub or exhaust duct with anything to catch
lint, except for UL approved vent basket.
Connecting to a ventilation duct
You will need a UL-CSA-approved, 4-inch
ridged metal exhaust duct. If a fl exible duct
is used, it must comply with the Outline for
Clothes Dryer Transition Duct. Subject 2158A
and maximum length of 2.4 m (8 feet).
NOTE!
• The more bends and the longer the
duct, the less air will circulate through
the machine, which will impede drying
performance. We recommend that you cut
off any excess exhaust duct and run the duct
with as few bends as possible. And make any
necessary bends as gentle as possible.
NOTE!
• Maximum duct length of 60 feet. A
maximum of 4 elbows may be used, but 4
feet of duct must subtracted from the total
vent length for every 90° elbow used.
NOTE!
• When installing in warm climates (77° F and
above) with high humidity levels, do not
route the air exhaust duct upwards.
subtract 4 feet for
every 90°elbow
Examples of
installations
To connect the exhaust duct to a
ventilation outlet, follow the steps below:
1. Connect the exhaust duct to a ventilation
exhaust fi tting or to a discharge through the
wall.
2. Secure the duct joint to the outlet stub on
the machine.
3. Run the duct with as few bends as possible
to the point of discharge.
Ventilation grill (not supplied with machine)
WARNING!
• This appliance shall not be exhausted into
a chimney, a wall, a ceiling, an attic, a crawl
space or a concealed space of a building.
Only a rigid or fl exible metal duct shall be
used for exhausting. Only a metal ventilation
grill shall be used. If the duct is taken to a
wall outlet, a ventilation grill shall be fi tted
to prevent reverse fl ow of cold air. Fit the
ventilation grill to the outside of the wall.
NOTE!
Avoid:
• very long exhausting systems
• too many corners
• tight corners
These reduce effi ciency and increase time and
energy consumption.
Electrical installation
WARNING!
• The receptacle on the rear of the machine
is designed to accommodate ASKO washers
ONLY (rated 208–240 V.) To use this
receptacle, you must use the ready-fi tted
plug supplied with the washing machine or
an equivalent.
ASKO washers rated 208–240 V have two
internal fuses of 15 A each.
The machine should only be connected to a
grounded wall socket.
WARNING!
• This appliance must be properly grounded.
Refer to the “Important Safety Instructions”
for grounding instructions.
The power supply cord must be grounded.
If the machine is to be used in a wet area,
the supply must be protected by a residual
current device.
Connection to a permanently wired supply
point must be made only by a qualifi ed
electrician. As supplied: Single-phase, 230
V, 60 Hz, 3000W heater rating 30 A circuit
required - only a power-supply cord kit
rated 230 V min, 30 A, and marked for use
with clothes dryers shall be used.
NOTE!
Do not connect the machine to the mains
electricity supply by an extension lead.
Remove cover to
access teminal box.
(Requires- Torx
screwdriver.)