1 3
INSTALLATION
POSIMATIC
10.1 Description of parameters
1: SETPOINT
Range of analog setpoint input (Voltage:0-10 V or current: 0-20 mA, 4-20 mA).
2: INIT ALL
Initialisation
Automatic initialisation is started by pressing the
+
or
-
and
→
→
→
→
→
keys (> 3sec). The individual steps of initialisation are
displayed with
„run 1
“ to
„run 5
“.
The positioner’s control parameters to drive the valve are optimised during initialisation.
3: DEFAULT STATE
Standard setting or recovery of factory settings and resetting of initialisation.
The positioner is set to „Default“ by pressing the
+
or
-
and
→
→
→
→
→
keys (> 3 sec).
The positioner must be initialised again after having been set to „Default“ .
All previous actuator parameters are deleted (initial state).
11: X-DIRECTION
Direction of manipulated variable.
Setting of the direction of action (rising or falling) of the display and position feedback.
12: ALARM FUNCTN
Activates or deactivates the alarm function.
The response threshold of the alarms (limit contacts) depends on the scale of POSITION (mechanical travel).
x = actual feedback value
i
Electropneumatic positioner: List of parameters
Display
Function
Parameter values
Unit
Factory settings
41: X-DISPLAY
Display of position
POSITION
%
POSITION
or flow
FLOW
42: DEADBAND
Size of dead zone
auto
auto
0.0...10.0
43: PROP GAIN
Proportional gain
10...1000
100
(PD positioner)
(K
p
= 0,1...10)
44: DERIV TIME
Differential time constant
10...1000
100
(PD positioner)
T
v
= 0,01 s ...1 s)
45: FIELDBUS
Fieldbus control
SETP.ANALOG
SETP. ANALOG
SETP. BUS
46: RELEASE
Software version
V XX
(XX = two-digit figure)
AIR SUPPLY
X-DIRECTION
Assigned
Chamber A1
feedback position x
Air exhaust
RISE
0 %
Air on
100 %
Air exhaust
FALL
100 %
Air on
0 %