Manual Load Transfer
This emergency procedure uses the electrically-operated Bypass Switch to transfer the load to the other source (if available).
It only can be used if the ATS is bypassed and isolated (racked out). The generator must be started via the
Engine Control
switch. There is a brief interruption to the load during transfer between sources.
Close enclosure door to prevent personal injury.
To Transfer the Load to Emergency Source
Bypassed to Normal
light is on.
Isolated
light is on.
1
Put
Engine Control
switch in the
RUN
position.
Generator starts. Let it warm up (according to
manufacturer’s guidelines).
Manual Engine Start Active
light is on.
Emergency Available
light comes on.
2
Press and hold the
Bypass
to Emergency
button. You
will hear the Bypass Switch
operate twice (first open then
close on emergency source).
Bypassed to Normal
light goes off.
Bypassed to Emergency
light comes on.
To Transfer the Load to Normal Source
Normal Available
light is on.
Bypassed to Emergency
light is on.
Isolated
light is on.
1
Press and hold the
Bypass
to Normal
button. You will
hear the Bypass Switch
operate twice (first open then
close on normal source).
2
Wait for generator to cool down (according to
manufacturer’s guidelines) before turning it off.
Then put
Engine Control
switch in the
AUTO
position. Generator stops.
Manual Engine Start Active
light is off.
Emergency Available
light goes off.
Figure 32. Engine control and Bypass controls
Press here