ASCO 4ATE, 4ACTE, 4ADTE, 4NTE, 4NCTE, 4NDTE
Installation Manual
Page 14
ASCO Power Technologies
381333-445 B
Unbypass
ATS is connected to Normal Source
1.
Press and hold the
Unbypass
button until the
Bypassed
to Normal
light goes off.
Figure 26. Unbypass to Normal button
Figure 27. Unbypass Normal diagram
Figure 28. Bypassed to Normal light off
The
Not in Automatic light will turn off.
ATS is connected to Emergency Source
1.
Press and hold the
Unbypass
button until the
Bypassed
to Emergency
light goes off.
Figure 29. Unbypass to Emergency button
Figure 30. Unbypass Emergency diagram
Figure 31. Bypassed to Emergency light off
The
Not in Automatic light will turn off.
The Bypass
Switch opens
its normal
contact
s.
The Bypass
Switch opens
its emergency
contacts.
This green light will shut off.
This red light will shut off.
The automatic transfer & bypass-isolation switch should be left in this position.