Installation Manual

 

 

 

 

 

381333-315 D 

ASCO Power Technologies 

Page 1 

Installation Manual 

The ASCO 5350 ATS Remote Annunciator is listed under the 
Underwriter’s Laboratories Standard UL-1008 for Automatic 
Transfer Switch accessories. This stand-alone device provides 
individual status monitoring and control of up to eight ASCO 
Automatic Transfer Switches (ATSs) over an ethernet 
network. Each ATS must have an ASCO 5150 Connectivity 
Module (CM) (Acc. 72E) connected to it. Daisy-chained ATSs 
that have ASCO 5110 Serial Modules (Acc. 72A) can share a 
single CM. The Catalog 5350 can communicate with these 
ATSs: 

 

7000 & 4000 Series (Group 5 Controller) 

 

Series 300 (Group 1 Controller) 

 

Series 185 (Group 4 Controller) 

 

ASCO 940 (Group 7 Controller) 

The ASCO 5350 complies with US UL requirements. It also 
has IEC Certification (CE Mark). 

Product Functions and General Descriptions: 

Separate light indicate switch status and position. 

ATS switch position 
ATS source availability 
ATS alarm condition 
ATS time delay active 

Separate push buttons individually initiate transfer switch 
operation and testing.  

ATS transfer test (

Transfer

)/ bypass (cancel) time delay 

Silence alarm 
Lamp test 
Reset 

The ATS Remote Annunciator can also be setup in multiple 
locations to monitor the same devices. This arrangement 
allows for redundant annunciation of business-critical ATSs. 

 

After the ATS Remote Annunciator is installed and 
configured refer to User’s Guide 381333-314. 

 
 

 
 
 

DANGER is used in this manual to warn of a 
hazard situation which, if not avoided, will result in 
death or serious injury. 

 
 
 
 
 

WARNING is used in this manual to warn of a 
hazardous situation which, if not avoided, could 
result death or serious injury. 

ATS Remote Annunciator 

Catalog 5350 

 

 

Rear view 

 

381333-315 D 

TABLE OF CONTENTS

page

Specifications

 .

 

 2

Installation

 .

 

 3

Functional Test

 .

 

 4

Configuration

 .

 

 5

ATS Configuration

 .

 

 7

Diagnostics

 .

 

10

Troubleshooting

 .

 

11

Installation Drawings & Wiring Diagrams
Index

 .

 

12

    

DANGER 

 

 

 

 

!

      

WARNING 

 

 

 

!

Summary of Contents for 5350

Page 1: ...light indicate switch status and position ATS switch position ATS source availability ATS alarm condition ATS time delay active Separate push buttons individually initiate transfer switch operation and testing ATS transfer test Transfer bypass cancel time delay Silence alarm Lamp test Reset The ATS Remote Annunciator can also be setup in multiple locations to monitor the same devices This arrangem...

Page 2: ...tings 1 A 110 220 V ac 50 60 Hz 1 Factory Default Information A label on the back to the ATS Remote Annunciator lists several important settings that you will need to do the configuration Write down this information below before installing it and after changing these settings IP Addr ______________ factory default 169 254 1 200 Login ______________ factory default admin and user see page 4 for Log...

Page 3: ...nals accept 30 to 12 AWG stranded flexible wire If the power wiring is solid wire pigtail it with stranded flexible wiring to the ATS Remote Annunciator Use a 3 mm flat screwdriver to tighten the power terminals screws to 5 in lb 0 5 Nm tightening torque To avoid shock burns or death deenergize all electrical sources before making connections 5 Internal Buzzer and Alarm Relay Refer to wiring diagr...

Page 4: ...P then click Properties 6 Set the IP setting of the laptop computer see Figure 2 IP Address 169 254 1 100 last digit must be different than ASCO 5350 Default IP Subnet Mask 255 255 0 0 same as ASCO 5350 Default Gateway leave blank This is needed only if communicating to a different LAN 7 Click OK and click Close Close the Local Area Connection window 8 Once the TCP IP setup is complete at the lapt...

Page 5: ...iguration 5 On the left pane under Configurations click Annunciator to configure the ATS Remote Annunciator See Figure 5 click Figure 5 Configurations Annunciator 6 The Configurations Annunciator screen appears See Figure 6 The configurations features are Annunciator name software upgrade IP address subnet mask gateway address port encryption buzzer mode Figure 6 Configurations Annunciator 2 1 Ann...

Page 6: ...e 8 Write which option is selected here___________________ Figure 8 Audible Alarm buzzer Mode The buzzer sounds in one second pulses not adjustable In the Continuous mode the pulsing buzzer sounds continuously on off cycles In the Periodic mode the duration of the pulses and interval between pulses can be set as follows Duration On Time 0 2400 minutes Interval Off Time 1 60 minutes See Figure 9 Fi...

Page 7: ...The Configurations ATS screen appears See Figure 13 Select either Single ATS or Multiple ATS based upon the communication architecture of the ATSs and press the corresponding Go button under the selection Single ATS connected to one Connectivity Module CM each ATS having its own Connectivity Module Multiple ATS connected to one Connectivity Module all ATSs connected through a single Connectivity M...

Page 8: ...ine the dash number on the microprocessor s label dash number 9 and higher is ASCObus 2 All ATSs must use the same protocol For ASCO 940 and 962 ATSs select G7 ASCO1 Figure 19 Controller Protocol manual selection Select the appropriate address that is set in the ATS controller G1 G5 or G7 Figure 20 Controller Address manual selection If a Power Manager PM is used the address must be the same as th...

Page 9: ...PM is provided with an ATS the PM s eight Status Inputs can be configured to signal an alarm at the ATS Remote Annunciator At the PM the Status Input must be set to ACTV on Refer to PM manual 381333 199 1 Be sure that a PM Address has been set Figure 21 Then click the Configure button Figure 23 next to PM Address 2 The first row top is for PM Status Input 1 Click Enabled 3 Next enter a name in the...

Page 10: ...creen 2 Alarm On the left pane under Diagnostics click Alarm to see the status of all ATS alarms that are configured See Figure 28 click Figure 28 Diagnostics Packet The Diagnostics Alarm screen shows if there any of these ATS alarms Communication Error ATS Locked Out 7ADTS 4ADTS Failure to Synchronize 7ACTS 4ACTS and Extended Parallel 7ACTS 4ACTS See Figure 29 Based upon which alarm has occurred ...

Page 11: ...ear a beep ATS Annunciator could have changed to default settings Refer to Installation Manual 381333 315 Use the configuration details entered on page 2 reconfigure the ATS Annunciator Password not set The password must be configured See Modbus Notes on page 8 5 Buzzer is beeping continuously Communication with the Power Manager may have stopped Refer to Installation Manual 381333 315 Check the E...

Page 12: ...ler password 8 custom ATS labels 2 D diagnostics 10 digital input 10 discover 11 F factory default information 2 firmware update 5 functional test 4 G gateway address 2 4 6 Group 5 controller 8 H HELP 800 800 2726 ASCO customercare asco com I initial checks 4 installation 3 internal buzzer and alarm relay 3 Internet Protocol 7 IP address 2 4 5 6 K key switch Control 11 refer to User s Guide 381333...