ASCO POWER TECHNOLOGIES 5350 Installation Manual Download Page 3

ASCO 5350 

 

Installation Manual

 

 

 

 

 

381333-315 D 

ASCO Power Technologies 

Page 3 

Installation 

The ASCO 5350 ATS Remote Annunciator can be panel 
mounted or attached to an electrical or masonry gang box. 
Refer to the installation drawing 834970 and wiring diagram 
834969 at the back of this manual. 

1 Panel 

Mounting

 

Refer to installation drawing 834970 sheet 1. After wiring the 
ATS Remote Annunciator, attach it (without the back cover) 
directly to the panel cutout. A gasket in the slot in the bezel 
provides Ingress Protection (IP51). Four screw adjustable 
mounting tabs are provided on the sides. Before inserting it 
through the opening, turn the four mounting screws counter- 
clockwise (to turn the tabs flush against the sides). After it is 
installed, turn the screws clockwise to extend the tabs, then 
tighten the four screws clockwise so that the tabs secure it 
from the inside. 
To release it, turn the four screws counter-clockwise until the 
tabs are loosened and then turn flush against the sides. 

2  Gang Box / Masonry Wall 
Mounting

  

Refer to installation drawing 834970 sheet 2. Before inserting 
it through the opening, turn the four mounting screws 
counterclockwise (to turn the tabs flush against the sides). 
After it is installed, turn the screws clockwise to extend the 
tabs, then tighten the four screws clockwise so that the tabs 
secure it from the inside. Install the wide bezel to cover the 
steel plate.  
To release it, turn the four screws counterclockwise until the 
tabs are loosened and then turn flush against the sides. 

3 Flush 

Mounting 

For flush mounting in 4-inch or deeper walls, mounting 
enclosure kit K871966-003 is required.  

4 Power 

Wiring 

A licensed electrician should install the ATS Remote 
Annunciator. All national and local codes must be followed. 

Refer to wiring diagram 834969. The power terminals accept 
30 to 12 AWG stranded flexible wire. If the power wiring is 
solid wire, pigtail it with stranded flexible wiring to the ATS 
Remote Annunciator. Use a 3 mm flat screwdriver to tighten 
the power terminals screws to 5 in-lb. (0.5 Nm) tightening 
torque.  

 

 
 
 

To avoid shock, burns, or death, deenergize all 
electrical sources before making connections. 

5  Internal Buzzer and Alarm Relay 

Refer to wiring diagram 834969. In addition to the internal 
alarm buzzer, a normally-open dry alarm contact is provided 
for an external buzzer circuit. An ac buzzer can be wired along 
with the main ac power supply. A dc buzzer requires a 24 V 
dc power supply and can be wired along with the 
communication wiring. See page 6 for configuration of buzzer 
operation. 

6  Communication Wiring (Ethernet) 

Refer to wiring diagram 834969. The communication wiring 
and ac power wiring must be isolated. Use Belden 1583A 
cable or equivalent UTP CAT 5e or CAT 6 with RJ-45 
connectors (untwisted pair or higher). Connect the Ethernet 
Ports to the network.  

6-1 Communication Architecture 

These architectures are applicable for ASCO 5350: 

Communication wiring for up to 8 ATSs for Single Location 
with individual Connectivity Modules for every ATS 

Communication wiring for more than 8 ATSs for multiple  
locations with individual Connectivity Modules for every ATS 

Communication wiring for up to 32 ATSs for multiple 
locations with single Connectivity Module for Group 5 
Controller (4000 & 7000 Series) 

Communication wiring for up to 32 ATSs for multiple 
locations with single Connectivity Module for Group 1 
Controller (Series 300) & Group 5 Controller (4000 & 7000 
Series) 

Communication wiring for up to 32 ATSs for multiple 
locations with single Connectivity Module for Group 7 
Controller  
(ASCO 940, 962) 

NOTE 
For best performance limit any RS-485 serial daisy-chain to 
eight ATSs. Each ATS Remote Annunciator is capable of  
handling a single serial communications string at a time, but is 
scalable by adding additional ATS Remote Annunicators. 

   

DANGER

 

 

!

Summary of Contents for 5350

Page 1: ...light indicate switch status and position ATS switch position ATS source availability ATS alarm condition ATS time delay active Separate push buttons individually initiate transfer switch operation and testing ATS transfer test Transfer bypass cancel time delay Silence alarm Lamp test Reset The ATS Remote Annunciator can also be setup in multiple locations to monitor the same devices This arrangem...

Page 2: ...tings 1 A 110 220 V ac 50 60 Hz 1 Factory Default Information A label on the back to the ATS Remote Annunciator lists several important settings that you will need to do the configuration Write down this information below before installing it and after changing these settings IP Addr ______________ factory default 169 254 1 200 Login ______________ factory default admin and user see page 4 for Log...

Page 3: ...nals accept 30 to 12 AWG stranded flexible wire If the power wiring is solid wire pigtail it with stranded flexible wiring to the ATS Remote Annunciator Use a 3 mm flat screwdriver to tighten the power terminals screws to 5 in lb 0 5 Nm tightening torque To avoid shock burns or death deenergize all electrical sources before making connections 5 Internal Buzzer and Alarm Relay Refer to wiring diagr...

Page 4: ...P then click Properties 6 Set the IP setting of the laptop computer see Figure 2 IP Address 169 254 1 100 last digit must be different than ASCO 5350 Default IP Subnet Mask 255 255 0 0 same as ASCO 5350 Default Gateway leave blank This is needed only if communicating to a different LAN 7 Click OK and click Close Close the Local Area Connection window 8 Once the TCP IP setup is complete at the lapt...

Page 5: ...iguration 5 On the left pane under Configurations click Annunciator to configure the ATS Remote Annunciator See Figure 5 click Figure 5 Configurations Annunciator 6 The Configurations Annunciator screen appears See Figure 6 The configurations features are Annunciator name software upgrade IP address subnet mask gateway address port encryption buzzer mode Figure 6 Configurations Annunciator 2 1 Ann...

Page 6: ...e 8 Write which option is selected here___________________ Figure 8 Audible Alarm buzzer Mode The buzzer sounds in one second pulses not adjustable In the Continuous mode the pulsing buzzer sounds continuously on off cycles In the Periodic mode the duration of the pulses and interval between pulses can be set as follows Duration On Time 0 2400 minutes Interval Off Time 1 60 minutes See Figure 9 Fi...

Page 7: ...The Configurations ATS screen appears See Figure 13 Select either Single ATS or Multiple ATS based upon the communication architecture of the ATSs and press the corresponding Go button under the selection Single ATS connected to one Connectivity Module CM each ATS having its own Connectivity Module Multiple ATS connected to one Connectivity Module all ATSs connected through a single Connectivity M...

Page 8: ...ine the dash number on the microprocessor s label dash number 9 and higher is ASCObus 2 All ATSs must use the same protocol For ASCO 940 and 962 ATSs select G7 ASCO1 Figure 19 Controller Protocol manual selection Select the appropriate address that is set in the ATS controller G1 G5 or G7 Figure 20 Controller Address manual selection If a Power Manager PM is used the address must be the same as th...

Page 9: ...PM is provided with an ATS the PM s eight Status Inputs can be configured to signal an alarm at the ATS Remote Annunciator At the PM the Status Input must be set to ACTV on Refer to PM manual 381333 199 1 Be sure that a PM Address has been set Figure 21 Then click the Configure button Figure 23 next to PM Address 2 The first row top is for PM Status Input 1 Click Enabled 3 Next enter a name in the...

Page 10: ...creen 2 Alarm On the left pane under Diagnostics click Alarm to see the status of all ATS alarms that are configured See Figure 28 click Figure 28 Diagnostics Packet The Diagnostics Alarm screen shows if there any of these ATS alarms Communication Error ATS Locked Out 7ADTS 4ADTS Failure to Synchronize 7ACTS 4ACTS and Extended Parallel 7ACTS 4ACTS See Figure 29 Based upon which alarm has occurred ...

Page 11: ...ear a beep ATS Annunciator could have changed to default settings Refer to Installation Manual 381333 315 Use the configuration details entered on page 2 reconfigure the ATS Annunciator Password not set The password must be configured See Modbus Notes on page 8 5 Buzzer is beeping continuously Communication with the Power Manager may have stopped Refer to Installation Manual 381333 315 Check the E...

Page 12: ...ler password 8 custom ATS labels 2 D diagnostics 10 digital input 10 discover 11 F factory default information 2 firmware update 5 functional test 4 G gateway address 2 4 6 Group 5 controller 8 H HELP 800 800 2726 ASCO customercare asco com I initial checks 4 installation 3 internal buzzer and alarm relay 3 Internet Protocol 7 IP address 2 4 5 6 K key switch Control 11 refer to User s Guide 381333...

Reviews: