ECOsaver V240SP
23
① Connect a hose with ball
valve to the discharge port
of the recovery machine and
close the ball valve.
② Set the valve to the“② VAPOR
RECOVERY” position.
③ Set the Auto stop/run switch
to the “Run” position.
④ Set the Power switch to the
“ON” position.
⑤ Push the Start switch.
⑥ Make sure the recovery
machines is stopped by the
high pressure switch and the
High pressure warning lamp
is on after a while.
Check the high pressure warning function
① Set the valve to the “④ OFF”
position during the recovery
machine is stopped by the
high pressure switch.
② Open the ball valve of the
discharge port.
③ Set the Auto stop/run switch
to the “Auto stop” position.
④ Set the Power switch to the
“ON” position.
⑤ Push the Start switch.
⑥ Make sure the recovery
machine stops automatically
when the suction pressure
reaches the vacuum area and
the Recovery complete lamp
is on.
Check the low pressure cut-off function
① Set the valve of the recovery
machine to the “ ② VAPOR
RECOVERY” position.
② Set the Auto stop/run switch
to the “Run” position.
③ Set the Power switch to the
“ON” position.
④ Push the Start switch.
⑤ Make sure the air is sucked
f r o m t h e s u c t i o n p o r t
and discharged from the
discharge port.
⑥ Set the valve of the recovery
machine to the “ ④ OFF”
position and make sure the
suction pressure reaches the
vacuum area.
Check the recovery function
① Set the valve of the recovery
machine to the “③ PURGE”
position.
② Set the Auto stop/run switch
to the “Run” position.
③ Set the Power switch to the
“ON” position.
④ Push the Start switch.
⑤ M a k e s u r e t h e s u c t i o n
p r e s s u r e r e a c h e s t h e
vacuum area and the air will
not be discharged from the
discharge port.
Check the purge function
Vacuum area
Suction pressure
Discharge
Discharge port
5
Suck
Suction port
5
6
Vapor
recovery
Valve
1
OFF
6
Purge
Valve
1
Discharge port
5
Vacuum area
Suction pressure
5
Air will not be
discharged
On
High pressure warning lamp
6
Stop
Recovery machine
Close
Ball valve
Ball valve
1
Vapor
recovery
Valve
2
Vacuum area
Suction pressure
6
On
Recovery complete lamp
6
OFF
Valve
1
Stop
Recovery machine
Open
Ball valve
Ball valve
2
MAINTENANCE &
INSPECTION