●  Use our original recovery cylinders.

●  Use cylinders on which the type of refrigerant to be recovered is mentioned.

●  Empty cylinders should be evacuated before use.

●  How to evacuate air (Vacuum pump is optional)

①  Connect the suction port of the vacuum pump 

to the vapor port of the cylinder with a hose.

②  Switch on the vacuum pump.
③  Close the liquid port of the cylinder and open 

the vapor port.

④  Close  the  vapor  port  of  the  cylinder  when 

the  vacuum  reaches  -72cmHg/-28inHg  to 

-76cmHg/-30inHg.

⑤  Switch off the vacuum pump.
⑥ Disconnect the hose between the vacuum pump 

and the cylinder.

3)Preparation of Cylinder

Liquid port

Vapor port

Suction

port

Recovery cylinder

Vacuum pump

●  How to shorten the recovery time

①  After liquid recovery is  completed, recover 

from both the liquid and the vapor ports.

②  Remove the valve cores of the service ports 

of the system if they have.

③  Remove the core depressors of the charging 

hoses.

④  Use large size 3/8” hoses.
⑤  Replace the gaskets of the hoses if they are 

deformed.

⑥  Recover  refrigerant  while  operating  the 

crank case heater of the system.

⑦  Heat  up  the  accumulator  by  a  heat  gun  or 

give it vibration if it is frozen.

⑧  Recover from multiple systems in one time.

●  How  to  avoid  rise  in  temperature  and 

pressure in the cylinder

①  Put  the  recovery  machine  in  a  well-

ventilated shady area.

②  Do  not  put  the  recovery  machine  and  the 

cylinder directly on the floor but put them 

away from the floor.

③  Cool down the cylinder with wet cloths.
④  Use Cooling Unit (optional accessory) (See 

page 19).

⑤  Reduce the suction pressure of the recovery 

machine (See page 19).

⑥  Replace the cylinder with an empty one.
⑦  Cool down the cylinder with the sub-cooling 

procedure (See page 19).

⑧  Use a 120L cylinder.

4)Helpful Information

HOW TO USE

◆  The cylinder is designed according to the specifications of the recovery machine.
  The cylinder may be overfilled and exploded if the appropriate cylinder is not used.

◆  Brand-new cylinders have nitrogen inside.
  Evacuation should be done after discharging nitrogen by opening the vapor valve.
◆  Do not evacuate air from cylinders which contain refrigerant.
  The refrigerant will be discharged to the air and the vacuum pump oil will blow out.
◆  Do not evacuate air from cylinders by using the recovery machine.
  The compressor may be damaged if it is run for a long time under vacuum.

CAUTION

CAUTION

Summary of Contents for ECOsaver V240SP

Page 1: ...REFRIGERANT RECOVERY MACHINE ECOsaver V240SP INSTRUCTION MANUAL Please read this manual before operating...

Page 2: ...her Air Conditioning Equipment 8 HOW TO USE 10 Preparation before Operation 10 Liquid Vapor Recovery Procedure 12 Push Pull Recovery Procedure 16 Recovery Procedure of R410A or When the Pressure of Re...

Page 3: ...d smoking during the work in process Cigarette light may creates Carbon Oxy Chloride and ignite fire Use protective eye glass and hand glove when disconnecting hoses If Freon gas was touch your skin o...

Page 4: ...generator is not large enough it may lead to heating smoking or fire See the machine plate or this manual for the detailed specifications Do not setup the machine at location where gasoline thinner or...

Page 5: ...por recovery procedure the compressor may be damaged Do not let visitors touch the machine Do not use the machine when the result is unpredictable Do not use the machine for purposes other than the or...

Page 6: ...he store where the machine was purchased Use our cylinders that are expressly made for recovery and recycling Evacuation should not be done when the Auto stop run switch is at the Auto stop position A...

Page 7: ...g hose BLUE 152cm Power cord Shoulder strap Filter Valve Auto stop run switch Start switch Tank full lamp Recovery complete lamp VAPOR RECOVERY START PURGE OFF LIQUID RECOVERY COMPONENTS OF THE MACHIN...

Page 8: ...032F ES006 Shoulder Strap ES253 Power cord ES305 Instruction manual IM0436 Operation manual IM0437 Model ECOsaver V240SP Code No ES641 Recovery method Compressed vapor recovery method Push Pull metho...

Page 9: ...Cordless Vacuum Pump 1 5CFM VP151 Useful where has no power source Cooling unit CL3 3 8 ES801 Improves the efficiency of recovery in summer climate recovery in a large volume or recovery of R410A by u...

Page 10: ...ase of refrigerant when Disconnecting hose Quick charging valve A Y18975 Can be used without leaking refrigerant Recovery speed improves without Schrader Charging hose plus with SealRight fitting Vari...

Page 11: ...o START The temperature of the cylinder may rise when the ambient temperature is high or R410A is recovered Lower the temperature and pressure of the cylinder according to page 11 4 Helpful Informatio...

Page 12: ...of the system Heat up the accumulator by a heat gun or give it vibration if it is frozen Recover from multiple systems in one time How to avoid rise in temperature and pressure in the cylinder Put the...

Page 13: ...quid Vapor Recovery Procedure 1 Connection of the hoses and cords System to be recovered Safety cable Manifold Filter When a cylinder with float sensor is used When a cylinder without float sensor is...

Page 14: ...vacuum set the valve of the recovery machine to the PURGE position When the discharge pressure reaches to vacuum again connect the hose to the liquid port of the cylinder Close the ball valve of the...

Page 15: ...ecovered Set the valve of the recovery machine to the START position Open Liquid valve of the cylinder and High Pressure valves Liquid side of manifold and the system Valve operation Operation End of...

Page 16: ...r switch to the ON position Push the Start switch Please refer to P20 How to Restart the Recovery Machine if the unit does not run smoothly and restart the unit Turn the valve of the recovery machine...

Page 17: ...cannot be applied Ask the manufacturer of the system if not clear 1 Connection of the hoses and cords Safety cable When a cylinder with float sensor is used High Low Safety cable Filter Sight glass op...

Page 18: ...ition Do not set the Auto stop run switch to the Auto stop position Air may be left in the machine If the Auto stop position is selected the recovery machine will stop automatically Set to the Run pos...

Page 19: ...RECOVERY position Set the Auto stop run switch to the Auto stop position Make sure there is no liquid flow in the sight glass Valve operation Operation End of operation Set the valve of the recovery m...

Page 20: ...linder Turn the valve slowly to the VAPOR RECOVERY position Adjust suction pressure with valve to 3 5 kg cm2 43 5 72 5psi Close the vapor valve of the cylinder when the pressure in the cylinder drops...

Page 21: ...n Set the Power switch of the recovery machine to the OFF position and reset the breaker after approximately 5 minutes Restart the recovery machine according to How to Restart the Recovery Machine 1 W...

Page 22: ...linder is under this condition and this chart is useful for field operation When a cylinder is almost full with liquid and no vapor the pressure rises rapidly even with a slight increase in temperatur...

Page 23: ...mp is on and the recovery machine stops when the cylinder is turned upside down Check the overfilling prevention function in case a cylinder with float sensor is used Connect the Safety cable to the c...

Page 24: ...on Set the Auto stop run switch to the Run position Set the Power switch to the ON position Push the Start switch Make sure the air is sucked f r o m t h e s u c t i o n p o r t and discharged from th...

Page 25: ...re in the cylinder is high Cool down the cylinder The piston seal is worn out Repair The cylinder valve is damaged Repair The hose has a core depressor Remove the core depressor in the hose The refrig...

Page 26: ...module Relay Red lamp Tank full Green lamp Reocvery complete lamp Low pressure switch High pressure switch Safety cable Transformer Relay Compressor Thermal protector Circuit breaker Power switch Grou...

Page 27: ...FLOW DIAGRAM Condenser Suction port Safety valve High pressure switch Discharge port Suction pressure gauge Discharge pressure gauge Low pressure switch Recovery Purge Purge Recovery Check valve Compr...

Page 28: ...Customer Memo Please ll in for your record in the future The information is helpful for inquiry and ordering parts Products Number Date Purchased Store Purchased the Unit Ver 01 Code No IM0436 V...

Reviews: