Page 9
daliGate quad User Guide
LED indication
daliGate quad features various LED indicators, which give different informational signals
depending on whether the product is booting up or in operational mode. The meanings are
explained below.
Net & Link LED:
OFF = Not connected
Yellow = Connected but no lighting data
Green = Art-Net / sACN on network
Power LED:
OFF = Not connected
Green (solid) = Good power
Green (flashing) = Identify
**
Red = Fault condition
DALI LEDs:
OFF = No data is being sent to this port
Green =
Lighting data is being output on this port
**
The Power LED will flash continuously
when the Identify command is sent by
DMX-Workshop. This enables daliGate
quad to be easily distinguished on a
network containing multiple nodes.
This LED will also blip briefly in response
to any programming command received
via the network.
During boot-up
During operation
y
Power LED
-
Slow flashing green (1Hz) = booting normally
-
Slow alternating green/red (1Hz) = factory start (settings cleared)
y
Power LED
-
Static green = powered, normal operation
-
Fast flashing green (5Hz) = identify
**
-
Occulting green = remote programming command received
-
Static red = fault condition
-
Fast alternating green/red (5Hz) = product is not commissioned (return for service)
y
Net & Link LED
-
Yellow = network link established (but
no lighting data)
-
Green = Art-Net or sACN detected
y
LEDs 1, 2, 3 & 4
-
Green = Data activity
y
All indicators
-
Off = mute command received