artisan
™
32
9.4 When the indoor temp. is locked, the indoor temp detection < temp setting “tS” + temp
difference “td”, the Indoor Temp. Lock would be unlocked immediately.
9.5 When the indoor temp lock “tL” finished, it will unlock. The function of indoor Temp Lock stops
until the indoor temp detection <temp. setting “tS” + temp. differenace “td” is detected again.
10. INDICATORS
:
10.1 Compressor : When the compressor is ON, the indicator is ON; when the compressor
is protection delay, the indicator is flashing; when the compressor is OFF,
the indicator is OFF.
10.2 Fan : When the fan is ON, the indicator is ON; when the fan is OFF, the indicator is OFF.
10.3 Defrost : Flashing during defrosting and OFF when non-defrost.
10.4 Power : The indicator is ON when the power is OFF; and the indicator is OFF when the
power is ON.
Function
Min
Max
Default
Description
tS
Setpoint (indoor temp.)
LS
HS
5°C
Indoor temp.
≤
setpoint, compressor stops.
td
Temp. Difference
1°C
10°C
4°C
Indoor temp.
≥
(tS+td), compressor starts to
operate.
dF
Defrost Cycle
0 Hr
99 Hr
6 Hr
dF=0; not defrost automatically, it only could
defrost manually.
dt
Defrost Period
0 Min
59 Min
30 Min
Defrost stops when defrost period finished.
Ds
Defrost Stop Temperature
-45°C
99°C
25°C
Even EVA temp.
≥
Defrost stopped temp.,
defrost will stop.
Dr
Drop Period
0 Min
15 Min
3 Min
When defrost stopped, drop period beginning
to count.
Ft
Fan Stop Temperature
-45°C
99°C
5°C
Even EVA temp.
≥
Fan stopped temp., fan
will stop.
gF
Defog Cycle
0 Hr
99 Hr
1 Hr
0: not defog automatically; but defog function
according to Power ON/OFF.
gt
Defog Period
0 Min
59 Min
15 Min
Defog stops when defog period finished.
AC
Compressor Delay Protection
0 Min
15 Min
3 Min
Even AC=0 It still has 1 min delay after power
supply.
HS
Max. Setpoint
tS
99°C
45°C
To limit the max setpoint.
LS
Min. Setpoint
-45°C
tS
-45°C
To limit the min setpoint.
At
Temp. Alarm Start Delay
0 Min
99 Min
60 Min
After startup, the temp alarm would be
delayed for a period of time.
AU
High Temp. Alarm (indoor temp.)
AL+1
99°C
70°C
Indoor temp.
≥
AU alarm delay starts to count
AL
Low Temp. Alarm (indoor temp.)
-45°C
AU-1
-45°C
Indoor temp.
≤
AL alarm delay starts to count
Ad
Temp. Alarm Delay Setting
0 Min
99 Min
30 Min
When the delay period finished, the temp.
alarm occurs.
Ot
Temp. Calibration (indoor temp.)
-8°C
7°C
0°C
Indoor temp. calibration
Ud
High and Low Voltage Alarm Delay
0 Min
99 Min
1 Min
Only high low voltage alarm counting would
delay 0: no detection
dL
Defrost Temp. Lock
0
1
0
0: no locked 1: locked
dd
Defrost Locked Display
0
1
0
0: display dF when locked
1: display temp. before defrost when locked
Lt
Defrost Locked Period
0 Min
30 Min
0
0: indoor temp.
≤
setpoint unlocked
1~30 min: unlocked according schedule
FC
Fan Operation Selection
0
1
0
0: fan continuous operate
1: fan operate with the compressor
SA
Alarm Mute
0
1
0
0: not muted when alarm 1: muted when alarm
tL
Indoor Temp. Lock
0 Min
60 Min
0
0: not locked 1~60 min: indoor temp. locked
Summary of Contents for LCF-411-RS
Page 1: ......
Page 3: ...artisan 2 ...
Page 8: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 7 ...
Page 22: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 21 ...
Page 26: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 25 ...
Page 30: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 29 ...
Page 41: ...artisan 40 Room Sensor black wire need to connect to PIN 1 for ground purpose WIRING DIAGRAM ...
Page 42: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 41 ...
Page 50: ...GENERAL OPERATING WARRANTY MANUAL FOR CHILLER FREEZER AND HEATED DISPLAY CABINETS 49 ...
Page 54: ......