ARTE NIREAS Installation & User Manual Download Page 9

I

NSTALLATION 

&

 USER MANUAL

  

 WATER HEATING FIREPLACE

 

| NIREAS 

 

8 | 

Page

 

 

5.4.4.

 

Connecting the fireplace with the flue 

t  is  necessary  that  the  flue  gas  tube  is  connected  to  a  certified  conduit  with  the  same 
diameter as the fireplace, by following the dimensions of the adjacent image.

 (Pic. 5.4.4.1)

For fireplace NIREAS the diameter of the flue is 180mm. The flue must be properly insulated 
with  stone  wool  with  thickness  of  4cm  with external  aluminum foil. 

Do  not use fiberglass  or 

paper  based  insulation

.  Also,  do  not  use  flexible  thin  walled  metallic  tubes  or  asbestos 

tubes. This tube should be perfectly sealed and well insulated throughout its length. 

To  install  the  flue,  you  must  place  it  on  the  fireplace  outlet  and  then  seal  it  using  the 
appropriate sealant. 

The  space  extending  around  and  over  the  device  up  to  the  deflector must  be  ventilated 
continuously.  For  this  reason  you  must  allow  cool  air  from  a  lower  spot,  for  example,  the 
bottom and the outlet of the hot air from above. 

(Pic. 5.4.4.2)

 

These  openings  must  remain  free  and  not  able  to  be  covered.  The  must  also  have  a 
minimum surface of 300 cm

2

, for example, a grille with size 30x10cm. 

This way you achieve: 

 

greater security 

 

increase on the heat of the room, due to the air circulating around the device. 

The hot air extract grille must be placed on top of the trunk approximately 20cm from the 
ceiling. The grille must always be installed, as its purpose is to allow, the heat that builds up 
inside the trunk to be released in the room and also to relieve the pressure created. 

The  hot  air extract  grille  can  also  serve  as  a  visiting  slot in  order for  the installer  or  the  user  to  have  access  to  the 
electronics  box  of  the  air  regulator  (STANDARD  type)  and  be  able  to  perform  maintenance,  like  changing  the 
rechargeable batteries. 

5.4.5.

 

Malfunction - Secure fireplace shutdown 

In rare occasions even a test fire may not cause sufficient draft in the flue. In this case contact your chimney sweep. 

Under no circumstances should you try to light a larger fire. If smoke escapes from the fireplace, ventilate the room immediately and contact 
your chimney sweep. DON’T LIGHT THE FIREPLACE! 

6.

 

C

ONNECTING 

N

IREAS TO THE CENTRAL HEATING INSTALLATION

 

ARTE® NIREAS fireplace can be installed to work individually or in collaboration with any another water heating device to be used for central or 
floor heating. 

 

 

To  ensure  the  safety  of  the  device  you  must  install  an  overheating  safety  valve 

(Pic.  6.1)

,  in  order  to  protect  the  system  against  possible 

overheating. Also in case of floor heating, it is necessary to use a buffer tank 

(Pic. 6.2)

 and a thermal mixing valve 

(Pic. 6.3)

 to ensure constant 

temperature of the water in the floor pipes. 

 

 

 

Pic. 6.1 

Pic. 6.2 

Pic. 6.3 

 

The installation is made by using 1 

1/4

” hoses. 

Pic. 5.4.4.1 

Pic. 5.4.4.2 

Summary of Contents for NIREAS

Page 1: ......

Page 2: ...preparation 14 7 3 3 Combustion air intake 14 7 3 4 Power failure 14 7 3 5 Heating during seasonal change or in adverse weather conditions 15 7 4 Adjusting the combustion air 15 7 4 1 Adjusting the c...

Page 3: ...ced locally which creates local employment and more tax revenues stay in the province 2 2 Buying firewood Where can I get my firewood Regenerated ready to burn firewood can be purchased from dealers F...

Page 4: ...rewood Avoid wood that pops chestnut conifers such as cedar spruce and pine as they may damage your fireplace or the flue Pay attention to the size of the logs Good firewood must have been cut at leas...

Page 5: ...on its insulation In average the required heat output for a properly insulated room and with external temperature of 0 is 40 kCal h per m3 Taking into account that 1kW equals 860 kCal h an equivalent...

Page 6: ...omising the secure transfer of our products 4 1 Unpacking the fireplace 1 The product will be delivered on a wooden palette which is lined with wooden side panels and top panel Pic 4 1 1 2 Firstly rem...

Page 7: ...rs Do not use ANY fuel other than the recommended 5 4 Flue security instructions Prior to installing the fireplace ARTE the chimney sweep or a qualified technician should check the condition and opera...

Page 8: ...e inclination and the distance of the chimney from the ridge according to the following table Pic 5 4 2 3 Inclination RIDGE CHIMNEY DISTANCE MIN HEIGHT ABOVE THE RIDGE m H m 15 1 85 m 0 50 m OVER THE...

Page 9: ...must be placed on top of the trunk approximately 20cm from the ceiling The grille must always be installed as its purpose is to allow the heat that builds up inside the trunk to be released in the roo...

Page 10: ...ons referring to national and European standards The installation can be set into operation only after it has been tested by a qualified inspector Prior to installing the new fireplace please contact...

Page 11: ...d only in case of heater map installation 13 Water pump 14 Automatic filling valve 15 Closed expansion tank 16 ARTE NIREAS fireplace 9 Fan coil heater 10 Radiator or heater mat 11 Temperature pressure...

Page 12: ...r map installation 13 Water pump 14 Automatic filling valve 15 Closed expansion tank 16 ARTE NIREAS fireplace 9 Fan coil heater 10 Radiator or heater mat 11 Temperature pressure gauge 12 Three way val...

Page 13: ...ge 12 Three way valve for by pass 5 Drainage 6 Water distribution box 7 Buffer tank 8 Hot water 1 Automatic vent valve 2 Thermometer 3 Overheating safety valve 4 ARTE NIREAS fireplace ARTE NIREAS fire...

Page 14: ...uipped with the following control systems 7 2 About ARTE NIREAS fireplace The fireplace that you just received is a device designed to offer excellent heating distribution in the area with a very high...

Page 15: ...ith external fresh air When you open the door of the combustion chamber for adding firewood there should be no pressure difference between outdoor and indoor air in the room so it is good to keep the...

Page 16: ...r intake damper To prevent overheating they are equipped with a sensor positioned in the copper tube Table 7 2 2 Line 10 of the water jacket where in the case of overheating the device closes the supp...

Page 17: ...o an outage longer than that an uninterruptible power supply device can be used UPS For safety reasons if the regulator is not receiving power the damper closes completely and is automatically placed...

Page 18: ...nages the DHW and HC pumps The table below presents the different modes of operation of the fireplace ICON MODE DESCRIPTION ON The air intake damper is automatically adjusted in order to stabilize the...

Page 19: ...e operation of another heat source e g gas boiler or to command an additional pump or solenoid when the water temperature reaches a predetermined value 7 4 2 5 TIME ADJUSTMENT screen The screen displa...

Page 20: ...the top of the buffer tank T1 The screen displays WAW temp sensor T1 damaged If the sensor is not installed the alarm is not activated Failure of the sensor on the bottom of the buffer tank T2 The scr...

Page 21: ...in order for enough air for combustion to enter Close the door again once the wood ignites 7 Ensure there is adequate air supply oxygen to maintain the flame clear and powerful when you reduce the amo...

Page 22: ...scharged directly through the draft of the flue to the exterior and not in the heating area ARTE NIREAS chamber manages to provide the maximum secondary combustion performance An automatic air intake...

Page 23: ...be stored in a closed container until cooled down or buried on the ground or dispersed somewhere 10 2 2 Glass ARTE NIREAS fireplace has a single ceramic glass in the window of the combustion chamber i...

Page 24: ...lean the flue chimney all the way from the fireplace to the flue end point above the house A good practice is to clean the flue after each operating season and to inspect it prior to the start to ensu...

Page 25: ...ttles inside the fireplace it forms rust which expands the more it settles This can cause excessive pressure on the fireplace joints thus causing damage NOTE It is recommended to thoroughly clean the...

Page 26: ...WATER HEATING FIREPLACE NIREAS 25 12 DIMENSIONS...

Page 27: ...Device dimensions W x D x H cm 77 5 50 128 Combustion chamber dimensions W x D x H cm 60 32 42 Flue draft Pa 12 Heated area m2 55 200 Weight kg 208 External air inlet The section must be increased by...

Page 28: ...artial failure to comply with the specifications contained in it ARTE also declines all responsibility resulting from an improper use of the appliance incorrect use by the user from unauthorized alter...

Page 29: ...INSTALLATION USER MANUAL WATER HEATING FIREPLACE NIREAS 28 Page NOTES S N S N...

Page 30: ......

Reviews: