- 82 -
P
OWERING ON FROM THE
M
AINS
¾
Set the “1/0” switch behind the door of the UPS in its “1” position.
After a few moments, the UPS is turned on, the capacitors are precharged and the "Lock / stand-by" LED blinks: The
UPS is in stand-by mode.
¾
Press the
button to access the power-on menu. When prompted to confirm, select “YES” and press the
button
again. All the LEDs around the display light up for about 1 sec. and a beep is emitted. The display shows the word
“POWER ON” to indicate the start of the power-on sequence at the end of which the UPS will enter “ON LINE” mode.
P
OWERING ON FROM THE
B
ATTERY
¾
Set the “1/0” switch behind the door of the UPS in its “1” position.
¾
Keep the “Cold Start” button (situated behind the door) pressed for about 5 sec. The UPS will be started and the
display turned on.
¾
Press the
button to gain access to the power-on menu. When prompted to confirm, select “YES” and press the
again. All the LEDs around the display light up for about 1 sec. and the buzzer starts to beep once about every 7
seconds.
Note:
if the sequence described above is not executed within 1 min., the UPS turns itself off to avoid discharging the
batteries unnecessarily.
P
OWERING OFF THE
UPS
From the main menu, select the “SYSTEM STBY” item and press
to gain access to the submenu and press it again to
confirm the operation. To turn the UPS off altogether, set the “1/0” switch in its “0” position.
Note
: during long idle periods, we recommend the UPS be turned off at the “1/0” switch and that all isolators
be opened.