47
Pictures for illustrating purposes only
MENU : CHANGING UNIT
CONFIGURATION
CONTROL SIGNAL IN
- - - - - - - - - - - - - - - - -
STEAM CAPACITY
LIMIT - - %
ADJUST PROP BAND
- - %
ADJUST SET POINT
- - %
MAINTENANCE FRE-
QCY - - - - - - - - KG
MAINTENANCE
INTERVAL - - - - H
Any press on the enter key
from any of these menus...
MENU: HUMIDIFIER
STATUS
Possible value :
1 step on/off digital control, digital sensor 4 steps, 0-
10V / 2-10V controler, 0-20 / 4-20 mA controler, 1-
5V sensor, Armstrong sensor
Possible value :
between 20 and 100 % if on/off control
Otherwise 50-100 %
Possible value : between 10 and 99 %
Possible value : between 1 and 50 %
Possible value : between 0 and 999000 kg
This allows to adjust the estimated number of produced
steam in kg or of working time before a visual control is
made. If a cylinder maintenance is to be done, please
refer to the cylinder maintenance pages of this manual. If
not, this parameter can be adjusted for a higher value
(factory default time : 300 h)
POWER OFF IF
DRAINING : - - - -
Possible value : YES or NO
This allows to shut down the contactor/s during
draining to prevent leakage currents
FOAM / SCALE
CONTROL - - SEC
Possible value : between 0 and 10 sec
This parameter allows to adjust the time of the small
drain that takes place whenever the humidifier takes water
in. This time can be increased when foam is seen inside
the cylinder (particularly when using softened wa-
ters).
SERIES EHU-750 HUMIDIFIER
System management -
Configuration changing menu