background image

installation &   

oper ating instructions

E.2 Series high efficiency    

 

circulator

4

read carefully before installing    

& operating the circulator
installer: 

please leave this manual for 

the owner’s use

You are about to install an 

e.2

 series circulator – a high– 

efficiency pump from Armstrong. 

e.2

 series circulators are 

designed for heating and cooling in hydronic, geothermal or 
solar systems and circulating water, ethylene or propylene 
glycol/water solutions. For pumping domestic (potable) water, 
Armstrong recommends the use of circulators with bronze, or 
stainless steel body construction.
The 

e.2

 series circulators are extremely efficient and quiet. 

They utilize a state of the art permanently lubricated bearing 
system designed for many years of trouble-free operation. 
They feature a permanent-split capacitor motor with thermal 
protection.

1.0  operating limits

Maximum operating pressure:  

150

 psi (

1034

 kPa)

Maximum operating temperature:

All standard models 

230°f (110°c)

Minimum operating temperature:

All standard models 

32°f (0°c)

Electrical rating:

For models with 

T

 hp motors 

(100w)

:

 

120 v

,

 1

 phase, 

60

 Hz or    

208

/

240 v

phase, 

60

 Hz, or 

220-240

v, 

50

Hz

For models with 

Q

 hp motors 

(300w)

:

 

120 v

phase, 

60

 Hz or 

208

/

240

/

277 v

1

 phase, 

60 

Hz, or 

220-240

v, 

50

Hz

When unpacking the circulator, inspect for any damage that 
may have occurred during transit. Check for loose, missing or 
damaged parts.

this pump is for indoor use only

Before installing the circulator, proper installation practice 
recommends a thorough flush of the hydronic system, ensuring 
removal of all foreign materials.

This pump should be installed in a well lit location with good 
access.

Installation personnel must be qualified for the task.

All personnel performing installation must wear appropriate 
personal protective equipment 

warning

Mount with motor shaft horizontal and terminal box 

above centerline (

cl

) only!

The circulator is supplied for up-discharge.

diagram 1:

 

Installation Orientation

cl

motor shaft

(internal)

For alternate discharge orientation:

1

  Loosen the four motor mounting bolts

2

  Rotate the volute to match piping orientation

3

  Observe flow direction arrow on volute

4

  Ensure volute gasket is properly seated

5

  Retighten mounting bolts evenly to 

lb/ft (

6.7 

N/m)

6

  Ensure the impeller spins freely

2.0  electrical wiring

The electrical wiring must be installed in strict ac-
cordance with the Canadian Electrical Code (Canada) 
or the U.S. National Electrical Code (USA),or 

bs7671

 

(Europe) as well as local codes and regulations.

1

  Electrical installation should be conducted by a qualified  

electrician. Installers should be equipped with proper  

 

personal protective equipment.

2

  The motors of 

e.2

 series circulators are designed for 

1

 phase,  

60

 Hz, 

120 v 60

 Hz, 

240 v 60

 Hz, 

220-240 50

 Hz service only. 

(Please refer to the rating label on the circulator’s terminal 
box to determine the correct voltage.)

3

  Always make sure the electric power is disconnected and    

locked out before wiring the circulator.

4

  To wire, loosen the screw from the terminal box cover and    

remove the screw and cover.

5

  Install the appropriate size conduit end to one of the holes 

on either side of the terminal box.

Summary of Contents for E.2 Series

Page 1: ...E 2 Series High efficiency circulator Installation and operating instructions File No 10 84 Date july 04 2018 Supersedes 10 84 Date january 25 2018...

Page 2: ......

Page 3: ...ectrical wiring 4 3 0 Start up 5 4 0 Preventive maintenance inspection 5 5 0 Pump replacement in an existing installation 6 5 1 Complete pump 6 5 2 Motor end only 6 6 0 Mechanical seal replacement 6 7...

Page 4: ...ecommends a thorough flush of the hydronic system ensuring removal of all foreign materials This pump should be installed in a well lit location with good access Installation personnel must be qualifi...

Page 5: ...4 230 v installations pump motor Pump motor thermally protected To auxilliary control if required Fusible disconnect or circuit breaker by others l1 l2 Typical wiring diagram for single phase 230 v 5...

Page 6: ...ed in the line 2 Ensure electrical power is disconnected and locked out 3 Close the water supply at the points closest to the pump s inlet and outlet 4 For safety allow water to cool to 100 f 40 c bef...

Page 7: ...loth and alcohol to ensure the surface is clean 14 Install the new rotating seal element and spring assembly by gently pushing it graphite ring first over the installation tool and onto the shaft unti...

Page 8: ...ressure 1034 kPa All models Electrical motor data model e7 2 e7 2b e9 2 e9 2b e12 2 e12 2b e14 2 e14 2b e22 2 e22 2b e33 2 e33 2b Nominal input voltage range 50 hz 220 240vac 220 240vac 220 240vac 220...

Reviews: