AMC-1222 CO/NO
2
Multidrop
8
7-3 TD DIP SWITCH:
5 minute alarm output activation time delay for CO sensor only.
7-4 MR DIP SWITCH:
Keeps the output signal on the last alarm level on for 5 minutes
longer after the alarm condition has cleared
7-5 DIP SWITCH:
Dip switch positions used to set the comfort zone sensitivity.
SW5(A) SW6(B) SW7(C) SW8(D) Sensitivity
7-6 A DIP SWITCHES:
OFF OFF OFF OFF Super High
7-7 B DIP SWITCHES:
OFF ON OFF ON High
7-8 C DIP SWITCHES:
ON OFF ON OFF Med
7-8 D DIP SWITCHES:
ON ON ON ON Low
8-A CO SPAN SIGNAL
ADJUSTMENT:
Sets the sensitivity of the CO sensor.
8-B NO
2
SPAN SIGNAL
ADJUSTMENT:
Sets the sensitivity of the NO
2
sensor.
8-C NO
2
ZERO SIGNAL
ADJUSTMENT:
Sets the zero NO
2
signal.
8-D CO ZERO SIGNAL
ADJUSTMENT:
Sets the zero CO signal.
9. INPUT
The input terminal block is used to connect additional sensor
modules. If input terminal block is not used, EOL is switched ON
10. OUTPUT
The output terminal block connects to the monitor or the input
terminal of another module.
11. CURRENT/VOLTAGE
JUMPERS
Configure between current or voltage output. Jumpers on “I” for
current output and on “V” for voltage output.
12. NO2 SPAN
CALIBRATION
JUMPER
Configure NO2 calibration gas concentration. Jumper on “A” for
normal and on ”B” for double gas concentration calibration.
Summary of Contents for AMC-1222
Page 3: ...AMC 1222 CO NO2 Multidrop 2 NOTE This page intentionally left blank...
Page 5: ...AMC 1222 CO NO2 Multidrop 4 2 PRODUCT INFORMATION Figure 2 1 AMC 1222 Sensor Module...
Page 12: ...AMC 1222 CO NO2 Multidrop 11 Figure 4 1 Transmitter Mounting Dimensions...
Page 13: ...AMC 1222 CO NO2 Multidrop 12 Figure 4 2 Pole Mount...
Page 20: ...AMC 1222 CO NO2 Multidrop 19 Figure 5 2 Calibration Procedure for 1222 NO2...