Armstrong Air BCE3M 18 Installation Instructions Manual Download Page 9

Page 9 of 18

Issue 1324

507120-01

Supply and return duct system must be adequately sized 

to meet the system’s air requirements and static pressure 

capabilities.  The duct system should be insulated with 

a minimum of 1” thick insulation with a vapor barrier in 

conditioned areas or 2” minimum in unconditioned areas. 

Supply plenum should be the same size as the flangedopening 

provided around the blower outlet and should extend at 

least 3 ft. from the air handler before turning or branching 

off plenum into duct runs.  The plenum forms an extension 

of the blower housing and minimizes air expansion losses 

from the blower. 

INSTALLING DUCT SYSTEM 

Install the conditioned air plenum, ducts and air filters (not 

provided) in accordance with NFPA 90B Standard for the 

Installation of Warm Air Heating and Air-Conditioning 

Systems (latest edition). 

Connect supply air duct to the flange on top of the air handler.  

If an isolation connector is used, it must be nonflammable.

 

A return air duct system is recommended.  If the unit is 

installed in a confined space or closet, a return connection 

must be run, full size, to a location outside the closet. 

Connecting Refrigerant Lines

 

Refrigerant lines must be connected by a qualified technician 

in accordance with established procedures.

1. 

Route  the  suction  and  liquid  lines  from  the  fittings 

on  the  indoor  coil  to  the  fittings  on  the  outdoor  unit.  

Run the lines in as direct a path as possible avoiding 

unnecessary turns and bends. 

2.  Make sure that the suction line is insulated over the 

entire exposed length and that neither suction nor liquid 

lines are in direct contact with floors, walls, duct system, 

floor joists, or other piping. 

3.  Connect the suction and liquid lines to the evaporator 

coil. 

4.  To avoid damaging the rubber grommets in the cabinet 

while  brazing,  slide  the  rubber  grommets  over  the 

refrigerant lines until they are away from the heat 

source. 

5.  Braze using an alloy of silver or copper and phosphorus 

with a melting point above 100°F. 

NOTE:

  

Do not use soft solder. 

6.  Reinstall the rubber grommets after brazing is finished.

 

7.  Make sure outdoor unit has been put in place according 

to the Installation Instructions and is connected to the 

refrigerant lines.

Sealing the Unit 

Seal the unit so that warm air is not allowed into the cabinet. 

Warm air introduces moisture, which results in water blow-

off problems.  This is especially important when the unit is 

installed in an unconditioned area. 

Refrigerant lines must be clean, dehydrated, refrigerant-

grade copper lines. Air handler coils should be installed 

only  with  specified  line  sizes  for  approved  system 

combinations.

Handle the refrigerant lines gently during the installation 

process.  Sharp bends or possible kinking in the lines 

will cause a restriction.

 

Do not remove the caps from the lines or system 

connection points until connections are ready to be 

completed.

  

IMPORTANT

There must be an airtight seal between the bottom 

of the air handler and the return air plenum.  Use 

fiberglass sealing strips, caulking, or equivalent sealing 

method between the plenum and the air handler 

cabinet to ensure a tight seal.  Return air must not 

be drawn from a room where this air handler or any 

gas-fueled appliance (ie., water heater), or carbon 

monoxide-producing  device  (ie.,  wood  fireplace)  is 

installed. 

  

WARNING

When sealing the cabinet, be sure to seal closed any  

space around the holes where the drain lines exit the 

cabinet using duct tape and/or Permagum.  Warm air  

must not be allowed to enter through any gaps or holes   

in the cabinet.

  

IMPORTANT

 

Unit Air Filter Size Chart 

Model 

 

Nominal Filter Size

-018   

 

   12” X 20” X 1

-024   

 

   15” X 20” X 1

-036   

 

   18” X 20” X 1

-042,-048 and -060  18” X 24” X 1

 

 

 

Summary of Contents for BCE3M 18

Page 1: ...Condensate Drain 7 Duct Systems and Filters 8 Connecting Refrigerant Lines 9 Sealing the Unit 9 Electrical Connections 10 Airflow Cooling Blower Speed 12 Check Out Procedures 13 Operation13 Maintenan...

Page 2: ...9 12 1 4 311 18 7 8 479 5 3 4 146 16 7 8 429 17 3 4 451 17 432 19 7 8 505 20 3 4 527 19 3 8 492 5 1 2 140 43 1092 18 1 2 470 22 559 6 152 16 406 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3...

Page 3: ...space routing requirements for refrigerant line condensate disposal filters duct system wiring and accessibility for service Refer to the air handler rating plate on the air handler for specific infor...

Page 4: ...s are provided for electrical wiring entrance For ease in installation it is best to make any necessary coil configuration changes before setting air handler in place For all performance testing units...

Page 5: ...ntal configuration is shown in Figure 3 5 If the unit is suspended the entire length of the cabinet must be supported If you use a chain or strap use a piece of angle iron or sheet metal attached to t...

Page 6: ...ugged Remove the plugs from the front drain pan ports 5 Re install modified coil drain pan assembly in air handler in the same orientation as before Figures 6 and 7 Figure 6 Install Main Drain Pan Mou...

Page 7: ...ure 9 On units of this type where the blower draws rather than blows air through the coil traps must be installed in the condensate drain lines primary and auxiliary if used Traps prevent the blower f...

Page 8: ...he drain pan to allow complete drainage of the pan NOTE Horizontal runs must have an anti siphon air vent standpipe installed ahead of the horizontal run See Figure 9 An extremely long horizontal run...

Page 9: ...oid damaging the rubber grommets in the cabinet while brazing slide the rubber grommets over the refrigerant lines until they are away from the heat source 5 Braze using an alloy of silver or copper a...

Page 10: ...t all power supplies 2 Remove the air handler access panel 3 Route the field supply wires to the air handler electrical connection box 4 Use UL listed wire nuts to connect the field supply conductors...

Page 11: ...Page 11 of 18 Issue 1324 507120 01 Figure 12 Low Voltage Connections 3 Speed PSC Motor...

Page 12: ...rom the 4 pin blower motor connector NOTE Reuse the factory installed plastic cap on whichever wire is not used 6 Replace all panels 7 Reconnect power CHANGE BLOWER SPEED NOTE Refer to wiring diagram...

Page 13: ...elay coil and then the indoor blower relay energizes The normally open contacts close causing the indoor blower motor to operate The circuit between R and Y is completed closing the circuit to the con...

Page 14: ...emperature of the cabinet The temperature humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal co...

Page 15: ...Page 15 of 18 Issue 1324 507120 01 Start Up and Performance Checklist Horizontal Configuration Figure 14...

Page 16: ...Issue 1324 507120 01 Page 16 of 18 Figure 15 Start Up and Performance Checklist Upflow Configuration...

Page 17: ...rnish the following information a complete model and serial number b proof of required periodic maintenance installation date and location and c an accurate description of the problem WARRANTY LIMITAT...

Page 18: ...odification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation of e...

Reviews: