Three Monthly Checks Maintenance Schedules
—
Repeat the monthly schedule.
—
Check blower wheels for dirt build-up and tightness on shaft.
—
Check all cabinet panels for correct fitting, alignment and seals, and clean cabinets
as required. Ensure no insulation has been detached from the panels.
—
All electrical terminals should be checked for tightness.
IMPORTANT – Ensure the with main switch is turned off.
—
Check and clean heat exchangers, heating/cooling coils, drain trays and outlets.
(If applicable). Vacuum or brush clean as necessary.
Annual Maintenance Schedules
—
Repeat monthly and three monthly checks.
—
Check cabinet for any paint chips or abrasions and treat accordingly.
—
Check and record the available voltage and amperage of each phase.
—
Check and record the amperage of each motor against nameplate details.
—
Check and record refrigerant gas pressures (if applicable).