ARLACON MC300
MC300MAE
Control system
User's manual
22
Product code 1003418
FERRITE RING
POWER CABLE
4 PASSES
THROUGH
FERRITE RING:
N=4
Fig. 2.6.5.1, Ferrite ring suppressor in power cable
If EN50081-1 levels for conducted emissions are necessary, use an additional RF filter
available from your Arlacon distributor.
2.6.6 MC300 flush mount connections,
Fig. 2.6.6.1 shows the recommended power supply and earth connections for MC300 flush
mount control unit.
Steel enclosure
MC300
flush
mount
24Vdc power supply
earth
bars
L
N
PE
TE
1
2
+24V
0V
S1
Ferrite
ring
n=4
TE
PE
enclosure
base
plate
ground
bars
isolated
from base plate
0V
+24V
connect
TE to PE if
TE not available
door
good
electrical
connection
good
electrical
connection
Ferrite
ring
n=4
I/O
such as
WAX2
optical fibres
outer shield connected
to enlosure wall or base plate near entry
inner shields connected
to TE near equipment
sensitive
external
cable
such as encoder