Examples of messages:
message 1: “Burglar alarm”
message 2: “Fire alarm”
message 3: “Medical assistance requested”
message 4: “Panic alarm”
message 5: “Care of Jones, 5 The High Street in Wolverhampton”
Start playback
All recorded messages can be played back through the connected telephone device.
☛
For the user.
After receiving an alarm call via the voice module, the dialler will generate a beep tone.
The user can then do the following:
1. Enter the
0
0
0
0
0
button on his telephone keypad. The connection is cut off.
2. Entering the
1
1
1
1
1
button to start a 45 sec Audio-listen-in period
3.6 Test call
The dialler is equiped with test call functions which can be activated automatically or manually.
3.6.1 Test delay hh
Set a “delay” time before the first automatic test call is sent to the central station. In this way the test calls
can be programmed a few days in advance (max.24 hours) to occur at a particular time in the week.
Example: You program the automatic test call for every 24 hours and you want the test call to be re-
ceived at the central station at 03:00 hrs. If you exit the installation at 17:00 hrs, you must therefore set
the DELAY to 10 hours. The first test is then sent at 03:00 hrs, and the subsequent tests are continued at
24-hour intervals (i.e. always at 03:00 hrs)
☛
The time starts as soon as the new parameters are accepted.
3.6.2 Test call time hhh
Program the length of time between two test calls in hours (from 0 to 254 hours).
3.6.3 Always Test
If this option is set to [NO], the dialler will only send a test call if no other messages have been sent
within the test call interval.