21
GB
TECHNICAL DATA
Power supply
Rated voltage
AC 230 V (±10%)
Rated frequency
50/60 Hz
Max. absorbed power
10 VA
Inputs
H/H digital inputs
Safety low voltage for low voltage contacts
and zero potential:
Open contact voltage DC 12 V
Closed contact current DC 3 mA
H1/H3 analogue inputs
Safety low voltage
Work range: DC (0...10) V
Internal resistance
>
100 kΩ
Probe input B9
NTC1k (QAC34)
probe inputs B1, B2, B3, B12, BX
NTC10k (QAZ36, QAD36)
Cables allowed for probe (Cu)
With cross-sectional area:
0.25 0.5 0.75 1.0 1.5 (mm
2
)
Maximum length:
20
40 60
80 120 (m)
Outputs
Relay outputs
Current fi eld
Activation peak
Max. total current (all relays)
Voltage fi eld
AC 0.02...2 (2) A
15 A for
≤
1 s
AC 6 A
AC (24...230) V (zero-potential outputs)
Summary of Contents for RVS 63
Page 102: ...102 103 104 107 108 110 118 120 121...
Page 103: ...103 6 1 2 4 5 3 4 3 60 4 6 1 5 2 230 50 L N H05 V2V2 F 3 2 3 4 a 1...
Page 182: ...182...
Page 183: ...183...