Ø 60/100 mm
F
IG
. 2.7
A
BC
D
E
F
G
J
K
HI
L
G
F
The boiler is designed to be connected to a coaxial flue discharge system.
9
2.9
F
LUE
C
ONNECTIONS
F
LUE
S
YSTEM
The provision for satisfactory flue termination must be made as described
in BS 5440-1.
The appliance must be installed so that the flue terminal is exposed to outdoor air.
The terminal must not discharge into another room or space such as an
outhouse or lean-to.
It is important that the position of the terminal allows a free passage of air
across it at all times.
The terminal should be located with due regard for the damage or
discolouration that might occur on buildings in the vicinity.
In cold or humid weather water vapour may condense on leaving the flue
terminal.
The effect of such “steaming” must be considered.
If the terminal is less than 2 metres above a balcony, above ground or above
a flat roof to which people have access, then a suitable terminal guard must
be fitted. When ordering a terminal guard, quote the appliance model
number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and
ventilation openings are specified in F
IG
. 2.6.
T
ERMINAL
P
OSTION
mm
A - Directly below an open window or other opening
300
B - Below gutters, solid pipes or drain pipes
75
C - Below eaves
200
D - Below balconies or car-port roof
200
E - From vertical drain pipes and soil pipes
75
F - From internal or external corners
300
G - Above ground or below balcony level
300
H - From a surface facing a terminal
600
I - From a terminal facing a terminal
1200
J - From an opening in the car port
(e.g. door, window) into dwelling
1200
K - Vertically from a terminal in the same wall
1500
L - Horizontally from a terminal in the same wall
300
F
IG
. 2.6