B004
TERMINAL POSITION
mm
A - Directly below an open window or other opening
300
B - Below gutters, solid pipes or drain pipes
75
C - Below eaves
200
D - Below balconies or car-port roof
200
E - From vertical drain pipes and soil pipes
75
F - From internal or external corners
300
G - Above ground or below balcony level
300
H - From a surface facing a terminal
600
I - From a terminal facing a terminal
1200
J - From an opening in the car port
(e.g. door, window) into dwelling
1200
K - Vertically from a terminal in the same wall
1500
L - Horizontally from a terminal in the same wall
300
A
BC
D
E
F
G
J
K
HI
L
G
F
Fig. 2.6
Ø 60/100 mm
The boiler is designed to be connected to a coaxial flue discharge system.
Fig. 2.7
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS
Morley Road
Tonbridge
Kent TN9 1RA
The minimum acceptable spacing from the terminal to obstructions and ventila-
tion openings are specified in Fig. 2.6