72 / GB
Power supplies of the indoor and the outdoor units are to be respectively connected to a Residual Current operated Circuit-Breaker
(RCCB) with threshold of 30mA. For inverter driven units (outdoor unit), it is advisable the use of type B residual current device for 3Ph
power supplies and type B or F for 1Ph power supplies (depending on the electrical system to which it is connected). For the units
without inverter, (indoor units) a type A Residual current device is sufficient. The type of connection must in any case be carried out in
a workmanlike manner by qualified personnel in compliance with the national regulations in force.
INTERNAL UNIT
WH – 1 ZONE
WH – 2 ZONE
WH - L
Electrical supply
V - ph - Hz
230 - 1 -50
400 - 3 -50
230 - 1 -50
400 - 3 -50
230 - 1 -50
400 - 3 -50
Admitted voltages field
V
196 ÷ 253
340 ÷ 440
196 ÷ 253
340 ÷ 440
196 ÷ 253
340 ÷ 440
Rated power input
kW
4
4
4
4
6
6
Max current
A
19.1
9.6
19.1
9.6
30
9.6
Thermal cutout - Circuit breaker
A
25 - C type
12-C type
13-C type
25 - C type
12-C type
13-C type
32 - C type
12-C type
13-C type
Differential circuit breaker size (RCCB)
mA
30 - A type
Supply cable dimensions *
Reference
H07RN-F
Min. cables section
3G6
5G2.5
3G6
5G2.5
3G6
5G2.5
Max diameter [mm]
18
17
18
17
18
17
Recommended cables
section
3G6
5G4
3G6
5G4
3G6
5G4
Max diameter [mm]
18
19.9
18
19.9
18
19.9
Wiring signal EDF, AFR, PV
mm
2
H05RN-F 2 x 0.75 mm
2
EBUS 2 cable
mm
2
H05RN-F 2 x 0.75 mm
2
* Cable length < 20m
Note:
It is strongly recommended to separate the supply cables from the communication cables.
Note:
To avoid interference problems in the connection between the EBUS 2 cable from the internal unit to the external unit, use a shielded cable.