88 / GB
MENU
SUB
-MENU
PAR
AME
TER
DESCRIPTION
RANGE
DEFAULT
17
1
0
HV Input 1
Not Defined
Absent
EDF
SG1
External switch off signal
Absent
17
1
1
HV Input 2
Not Defined
Absent
DLSG
SG2
External switch off signal
Absent
17
1
2
HV Input 3
Not active
PV Integration Active
Not active
17
1
3
AUX Input 1
None
Humidistat sensor
None
17
1
4
AUX Output 1 (AFR)
None
Fault alarm
Humidistat alarm
External heat request
Cooling request
None
17
1
5
AUX Output 2
None
Fault alarm
Humidistat alarm
External heat request
None
17
1
6
AUX P2 circulator setting
Auxiliary circulator
Cooling circulator
Buffer circulator
Auxiliary circulator
17
2
Energy manager parameter 1
17
2
0
Hydraulic scheme
None
Plus
Compact
Flex
Hp Water Heater
Light (NOT USED)
None
17
2
1
Thermoregulation
Absent
Present
Present
17
2
2
ECO / COMFORT
Eco Plus
Eco
Average
Comfort
Comfort Plus
Average
17
2
3
FlowT HP Offset
0 ÷10°C
2°C
17
2
4
Boost Time
0 ÷ 60 min
16 min.
17
2
5
External temperature correction
- 3; + 3°C
0°C
17
2
6
Active Resistance Stages
1 Stage
2 Stages
3 Stages
2 Stages
17
2
7
Pro-Tech anode active
OFF - ON
OFF
17
2
9
Antiblocking pump enable
OFF - ON
ON
17
3
Central Heating
17
3
0
CH pump prerun time
30 ÷ 255 sec.
30 sec.
17
3
1
Time for prerun new attempt
0 ÷ 100 sec.
90 sec.
17
3
2
CH Pump Overrun
0 ÷ 16 min.
3 min.
17
3
3
Pump Speed Control
Low speed
High speed
Modulating
Modulating
17
3
4
Delta T Pump Setpoint
5 ÷ 20°C
5°C
17
3
5
Min Pressure
0,3 ÷ 0,4 bar
0,4 bar
17
3
6
Warning Pressure
0,4 ÷ 0,8 bar
0,6 bar
17
3
7
Max PWM Pump
min PWM ÷ 100%
100%
17
3
8
Min PWM Pump
20% ÷ max PWM
40%