7. Refrigerant Cylinder Filling Procedure (Refrigerant Transfer)_
The cylinder (12) may be filled with refrigerant by the following procedures.
Connect the suction (blue) service hose (5) to storage cylinder liquid valve by using the
refrigerant cylinder adapter (provided from refrigerant supplier), open liquid valve on storage
cylinder, open service hose quick coupling (5) and console blue hand valve (4)...
Press "UP" key once to select the RECOVERY /
TRANSFER function and press "START". By using
“DOWN” key select TRANSFER (REFRIGERANT)
and press “START”.
Now, select from two options:
- TOTAL TRANSFER (all refrigerant) or,
- PARTIAL TRANSFER (set the amount of
refrigerant to be transferred).
Press "START" key and unit will automatically transfer refrigerant from storage cylinder to the
unit cylinder (12).
When the selected amount of refrigerant is transferred, close the storage cylinder valve and
allow the unit to recover the refrigerant from the service hose (5). Once the function is
completed the unit will display symbol "DONE" and the amount of refrigerant transferred will be
displayed in kg or lb on main display (2).
Important: Always keep a minimum of 2 kg in the cylinder (12).