![ARI ARI-PACO 2G Operating And Installation Instructions Download Page 37](http://html1.mh-extra.com/html/ari/ari-paco-2g/ari-paco-2g_operating-and-installation-instructions_2969558037.webp)
- Translated original instructions -
0040501006 2422
Page 2-37
Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
5.7.4.3 Bus termination resistance
Fig. 24
5.7.4.4 Switch assignment
Parity/Baud
The first two DIP switches of the 5-switch block determine the parity and the number of stop bits for
communication. DIP switches 3 to 5 define the baud rate.
The communication parameters such as parity,
baud rate and Modbus address are set by means of
DIP switches on the bus card.
Fig. 25
Function
DIP-Switches
Parity
Baud
1
2
3
4
5
Event parity, 1 stop bit (default)
0
0
Odd parity, 1 stop bit
0
1
No parity, 2 stop bits
1
0
No parity, 1 stop bit
1
1
2400 bps
0
0
1
4800 bps
0
1
0
9600 bps
0
1
1
19200 bps
1
0
0
38400 bps
1
0
1
57600 bps
1
1
0
76800 bps
1
1
1
115200 bps (default)
0
0
0
ON