![ARI ARI-PACO 2G Operating And Installation Instructions Download Page 20](http://html1.mh-extra.com/html/ari/ari-paco-2g/ari-paco-2g_operating-and-installation-instructions_2969558020.webp)
Page 2-20
0040501006 2422
- Translated original instructions -
Operating and installation instructions
Thrust actuator ARI-PREMIO
®
-Plus 2G
5.3 Mounting to valves
A
Mount adapter parts
Setting dimension (Y) and fitting-projection (X) are measured with inserted valve spindle!
2-way:
3-way:
B
Place actuator onto valve
C
Drive actuator spindle onto valve spindle
a
Yoke version
b
Column version
a
2,2 - 5 kN
b
12 - 15 kN
D
Screw the coupling
E
Secure coupling in place with grub screw
(a), clip lift dial (b) and position it (c)
ATTENTION !
connecting thread up to M16:
X = 60/83 mm
→
Y = 102 mm
(+2 mm)
X = 98 mm
→
Y = 116 mm
(+2 mm)
with adapter from M20 to M16:
X = 60/83 mm
→
Z = 128 mm
→
Y
=
146mm
X = 98 mm
→
z = 143 mm
→
Y
=
161mm
threaded bush 25 kN:
X = 83/98 mm
→
Y = 98 mm
hexagon nut
valve spindle
hexagon nut
valve spindle
hexagon nut
valve spindle
adapter
valve spindle
hexagon nut
threaded bush
turn
turn
Coupling 25 kN
b
a
c