Specifications for Argus’ Switched Mode Rectifier Cordex 48-1kW
010-606-B1 Rev A WC
Page 1 of 3
Power Module Output
Voltage:
40.5 to 58Vdc within rated limits
Current:
18.5A @ 54Vdc nominal (20.8A maximum @ 48V)
Maximum Power:
1000W continuous/module
Static Load Regulation:
Better than ±0.5% for any load change within rated limits
Dynamic Load Regulation:
Better than ±2% for 10% - 90% load step
(output shall recover to static limits within 2ms)
Static Line Regulation:
Better than ±0.1% for any change in input voltage within rated limits
Dynamic Line Regulation:
Better than ±1% for any change in input voltage within rated limits
(output voltage shall recover to static limits within 2ms)
Hold-up Time:
10ms
Time Stability:
≤
0.2% per year
Temperature Stability:
≤
100ppm/°C over the operating range
Heat Dissipation:
<340BTU per hour (per rectifier module)
Electrical Noise:
<26dBrnC (voice band) without battery
≤
22dBrnC (voice band) with battery
<5mVrms to 100MHz (wideband)
<100mVp-p to 100MHz
<2mV (psophometric)
Acoustic Noise:
<55dBa @ 1m (3ft.) @ 30°C (86°F) [individual module]
<55dBa @ 1m (3ft.) @ 30°C (86°F) [four modules]
EMI:
The unit meets requirements of EN55022 (see Standards for more EMC)
In accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines for
conformance to Part 15, Class B:
NOTE:
This equipment has been tested and found to comply with the limits for a Class B digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in a residential installation. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with
the instructions, may cause harmful interference to radio communications. However, there is no
guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
•
Reorient or relocate the receiving antenna.
•
Increase the separation between the equipment and receiver.
•
Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
•
Consult the dealer or an experienced radio/TV technician for help.
Any changes or modifications to this equipment not expressly described in this manual could void the FCC
compliance.
Summary of Contents for ALPHA OUTBACK ENERGY Cordex 48-1kW
Page 1: ...Cordex 48 1kW 19 Shelf Flush Mounting Up To 3000W With Distribution 030 713 B2 ...
Page 14: ...This page intentionally left blank ...
Page 38: ...03071305B__ sch 1 Mon May 14 15 17 29 2007 ...
Page 39: ...03071305B__ sch 2 Mon May 14 15 17 32 2007 ...