Specialist’s Manual 

 
Aptitude requirement for maintenance man (repairs. should be done only be specialists).  
a) Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate 
from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in 
accordance with an industry recognised assessment specifìcation.  
b) Servicing shall only be performed as recommended by the equipment manufacturer. Maintenance and repair requiring 
the assistance of other skilled personnel shall be carried out under the supevision of the person competent in the use of 
flammable refrigerants.  
Safety preparation work  
The maximum refrigerant charge amount is shown on the following table a  
(Note: Please refer to the nameplate for the charging quantity of R290) 
 

Room area (m2) 

11 15 

Maximum charge (kg) 

<0.152 0.225 

0.304 

table a - Maximum charge (kg) 

 

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the 
risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be complied with prior 
to conducting work on the system. 

 Work 

procedure 

Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour being 
present while the work is being performed. 

 

General work area 

AII maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. 
Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the 
conditions within the area have been made safe by control of flammable material. 

 

Checking for presence of refrigerant 

The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is 
aware of potentially toxic or flammable atmospheres. Ensure that the leak detection equipment being used is suitable for 
use with all applicable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe. 

 

Presence of fire extinguisher 

lf any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing 
equipment shall be available to hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area. 

 

No ignition sources 

No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any 
sources of ignition in such a manner that it may lead to the risk of fire or explosion. AII possible ignition sources, 
including cigarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and 
disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area 
around the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "No 
Smoking" signs shall be displayed. 

 Ventilated 

area 

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any 
hot work. A degree of ventilation shall continue during the period that the work is carried out. The ventilation should 
safely disperse any released refrigerant and preferably expel it externally into the atmosphere. 

 

Checks to the refrigeration equipment 

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all 
times the manufacturer's maintenance and service guidelines shall be followed. lf in doubt, consult the manufacturer's 
technical department for assistance.  
The following checks shall be applied to installations using flammable refrigerants:  
---The actual refrigerant charge is in accordance with the room size within which the refrigerant containing parts are 
installed;  
---The ventilation machinery and outlets are operating adequately and are not obstructed;  
---lf an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;  
---Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;  
---Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance 
which may corrode refrigerant containing components, unless the components are constructed of materials which are 
inherently resistant to being corroded or are suitably protected against being so corroded. 

 

Checks to electrical devices 

Repair and maintenance to electrical components shall include initial safety checks and component inspection 
procedures. lf a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until 
it is satisfactorily dealt with. lf the fault cannot be corrected immediately but it is necessary to continue operation, an 
adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are 
advised.  
lnitial safety checks shall include:  
---That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;  

Summary of Contents for LILIUM ART 11

Page 1: ...UCTIONS Read the instructions carefully before operating or servicing the dehumidifier Observe all the safety instructions failure to observe the instructions may lead to accidents and or damage Keep these instructions in a safe place for future reference EN ...

Page 2: ...n different ways other than those recommended by the manufacturer Should repair be necessary contact your nearest authorized Service Centre Any repairs carried out by unqualified personnel may be dangerous The appliance has to be stored in a room that doesn t have any continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not p...

Page 3: ...they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall not be made by children without supervision Make sure the plug is inserted fully Do not use multiple adapters Do not touch the plug with wet hands Make sure the plug is clean Children aged be...

Page 4: ...s water leaks can cause it to malfunction or cause excessive vibration and running noise The dehumidifier must be positioned at least 50 cm away from the wall or other obstacles so that the heat can dissipate correctly Close all open windows to maximise dehumidification efficiency Do not insert objects or sharp instruments into the air outlet grille Do not cover the air intake and outlet grilles i...

Page 5: ...ng so can cause leaks and malfunction In the event of interference with other electrical appliances place the two products at a minimum distance of 70cm DESCRIPTION OF PARTS 1 Control panel 8 Side panel 2 Colored LED with humidity sensor 9 Air inlet and air filter 3 Front panel 10 Water tank 4 Casters 11 Water outlet 5 Side panel 12 Air outlet 6 Handle 13 Power cord 7 Rear panel FRONT VIEW REAR VI...

Page 6: ...t is in operation If you wish to make continuous draining of condensate follow the instructions in the dedicated paragraph OPERATING PRECAUTIONS The dehumidifier starts only if the humidity level in the room is higher than 3 the set one The dehumidifier will continue to operate until the set humidity level is reached except for any interruptions due to filling the tank When the water tank is full ...

Page 7: ...ich is inside the tank is correctly positioned Make sure not to damage the float and the locking rivet which are inside the tank otherwise the unit will not automatically stop working when the water tank is full and the water could leak out and risk wetting the tank floor and damage the appliance N B Do not use the drainage pipe when you want to collect the condensate in the tank otherwise the wat...

Page 8: ...lay then set the desired humidity level During operation the Power symbol on the display remains always on and the display shows the humidity level detected in the room during operation of the dehumidifier By pressing this button again the unit stops working and the ventilation stops 2 MODE BUTTON The unit works in the following circular sequence Auto Mode Continuous Mode Sleep Mode the correspond...

Page 9: ...howing the humidity level detected in the environment To deactivate the Timer 00 must appear on the display flashes 4 times and the Timer symbol on the display will turn off 5 SPEED BUTTON VENTILATION SPEED It is possible to adjust the ventilation speed only in Auto mode Press this button to adjust the speed from high to low the corresponding symbols will light up on the display according to the s...

Page 10: ...ly then insert it back into its housing Do not use hair dryer or fire to dry the filter Do not use sponges or brushes to clean the filter as they can damage it 2 2 Reposition the filter by inserting it as indicated by the arrow and replace the water tank Do not use the dehumidifier without the filter as dust may affect the efficiency of the evaporator resulting in higher energy consumption CONSERV...

Page 11: ...d and the dehumidifier stops REGULATION EU N 517 2014 F GAS LILIUM ART 11 The unit contains R290 a natural greenhouse gas with global warming potential GWP 3 Kg 0 045 0 000135 Tons CO2 equiv Do not release R290 into the atmosphere LILIUM ART 13 The unit contains R290 a natural greenhouse gas with global warming potential GWP 3 Kg 0 050 0 000150 Tons CO2 equiv Do not release R290 into the atmospher...

Page 12: ...se any sources of ignition in such a manner that it may lead to the risk of fire or explosion AII possible ignition sources including cigarette smoking should be kept sufficiently far away from the site of installation repairing removing and disposal during which refrigerant can possibly be released to the surrounding space Prior to work taking place the area around the equipment is to be surveyed...

Page 13: ...ceptable for all refrigerant systems Electronic leak detectors may be used to detect refrigerant leaks but in the case of flammable refrigerants the sensitivity may not be adequate or may need re calibration Detection equipment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipm...

Page 14: ...ed refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked Labelling Equipment shall be labelled stating that it has been de commissioned and emptied of refrigerant The label shall be dated and signed For appliances containing flammable refrigerants ensure that there are labels on the equipment stating the equipment contains flammable refrigerant R...

Reviews: