Argo AT062310B Installation Procedure Download Page 4

8

connEcTing ELEcTricAL poWEr suppLy

Wiring THE BoiLEr

!

  

WARNING

Do not use aluminum wire!!

Argo Electric Hydronic Boilers are pre-wired for use with 

240-volt, 3 wire, single-phase, 50/60-hertz power. See 

Table A on page 4 for reduction in boiler capacity when line 

voltage is less than 240 volts.

Opening provided in jacket bottom panel for field wiring, 

refer to rating chart for recommended wire sizes.

Electrical wiring shall be done in accordance with Canadian 

Electrical Code, CSA C22.1 Part 1, authority having 

jurisdiction in Canada, or National Electrical code, ANSI/

NFPA 70 and/or authority having jurisdiction in USA. Verify 

nameplate rating and check related codes to properly size 

conductors, switches and over current protection. Several 

openings are provided on bottom of cabinet for different 

voltage connections. Wire connections refer to wiring 

diagram on inside of boiler front cover.

All circuit breakers or disconnects ahead of boiler must 

be OFF. If boiler contains integral breakers (depending on 

option), it is recommended they are also turned off at this 

time. Remove boiler front cover by removing 4 screws from 

top and sides.

If boiler is used in multiple zone system, the zone valves 

must be powered from independent source and have 

electrically isolated end switches or isolating relays wired in 

parallel to boiler thermostat terminals. 

Do not attempt to 

power zone valves from transformer in boiler control 

system!!

Wiring on conTroL

PUmP:

 

Connect  only  120  Vac  1/6  HP  (maximum) 

pump to terminals C1(L) and C2(N) on controller. Strip 

wire ends before inserting into terminal block. Tighten 

terminal  screws. 

Do  not  use  pump  rated  greater 

than 5 amps!!

tHERmoStat: 

Connect  thermostat  or  zone  valve 

end switch to terminals TT and TT 

(Figure 4)

Do not 

apply external power source to terminals!! 

Strip 

wire ends before inserting into terminal block. Tighten 

terminal screw clamps.

Field Wire Line Side Torque Specifications - 

table C

Wire Size (AWG)

Torque requirements (in LBS)

2/0-6

120

8

40

10-14

35

figurE 4

fiELd Wiring

Wire Classes - Table B

Number of Concentric Strands

Wire Size AWG

Class B

Class C

10

7

19

8

7

19

6

7

19

4

7

19

3

7

19

2

7

19

1

19

37

1/0

19

37

2/0

19

37

Class B - Power cables

Class C - Power cables where more flexibility is desired

All Field wiring shall be in accordance with NEC or CEC 

• 

standards. Minimum Circuit Ampacity (MCA) and recom-

mended Maximum Overcurrent Protection (MOP) are list-

ed on nameplate of unit, see Table A.
Use Copper conductors only.

• 

Use only Class B or C Stranded wire. See Table B.

• 

Wire Strip Length: 11/16” (Minimum). (Refer to field wir

-

• 

ing diagram).
Wire must be fully inserted into terminal block, touching 

• 

back of entrance hole. 
Field terminal wire lugs shall be tightened in accordance 

• 

with  manufacture's  recommended  torque  specifications 

using appropriate torque wrench. Proper toque settings 

are listed on terminal block, see Table C.
Hex head wrench size required for Terminal Block: 5/16”. 

• 

For Circuit Breaker: Flat Screwdriver.
Do not use wire grease on wire termination connections 

• 

and  terminal  block.  This  will  change  torque  properties. 

The Terminal block was not tested or approved using wire 
grease.

fiELd Wiring diAgrAm

Hold lug at specified torque for 5 seconds before releasing. 

• 

When tightening this will ensure any cold flow of material 

is compensated for.

Summary of Contents for AT062310B

Page 1: ...ting brackets for easy wall mounting Use of lag screws or anchor bolts through holes provided or on 3 4 plywood panel On uneven walls suggested mounting surface be provided such as two 2 x 4 s Surface...

Page 2: ...p supply may be located in this area below Circulator pump should be installed on supply side pumping away 6 Install gate valves at locations shown in Figures 2 3 so any boiler servicing requiring rem...

Page 3: ...7 primary secondary piping for Multiple zoning with ZONE VALVES primary secondary piping for Multiple zoning with circulators PRIMary secondary piping figure 2 figure 3...

Page 4: ...e ends before inserting into terminal block Tighten terminal screws Do not use pump rated greater than 5 amps Thermostat Connect thermostat or zone valve end switch to terminals TT and TT Figure 4 Do...

Page 5: ...re sizes specified conform to Canadian Electrical Code Canada or National Electric Code USA and include derating for ampacity and temperature Use copper wire only Check state and local requirements Re...

Page 6: ...or will continue to be energized for 3 minutes to purge boiler After 3 minutes control will de energize circulator Circ LED turns off If during start up or during operation safety end switch opens its...

Page 7: ...TACT SEC 120 VOLT WIRING POSE DES C BLES 120 VOLT 240 VOLT WIRING POSE DES C BLES 240 VOLT 120 VOLT FIELD WIRING POSE DES C BLES 120 VOLT SUR EN CHANTIER 240 VOLT FIELD WIRING POSE DES C BLES 240 VOLT...

Page 8: ...HERS SOURCE DU COURANT 120V 60HZ 1PH OU AUTRES OPTIONAL FLOW SWITCH BY OTHERS INTERRUPTEUR DE D BIT FACULTATIF OU AUTRES THERMOSTAT BY OTHERS THERMOSTAT OU AUTRES ELEMENT 1 L MENT No1 ELEMENT 1 RELAYS...

Page 9: ...T BLK BLANC NOIR WHT BLANC FUSE BLOCK BLOC DE FUSIBLE BLK NOIR L2 L1 POWER BLOCK BLOC DE PUISSANCE 240 VOLT FIELD WIRING POSE DES C BLES 240 VOLT EN CHANTIER EN CHANTIER 120 VOLT WIRING POSE DES C BLE...

Page 10: ...NOIR WHT BLANC RED ROUGE WIRE LEGEND L GENDE DES FILS DRY CONTACT WIRING POSE DES C BLES DE CONTACT SEC 120 VOLT WIRING POSE DES C BLES 120 VOLT 240 VOLT WIRING POSE DES C BLES 240 VOLT 120 VOLT FIELD...

Page 11: ...as the pressure remains less than 25 PSIG Hydronic block is now ready to be put into service Verify hydronic block circuit breaker or switch at service 1 entrance and depending on option hydronic blo...

Page 12: ...cluded with this manual Turn off hydronic unit circuit breaker at service en 1 trance and or disconnect switch Close gate valves near inlet and outlet of hydronic 2 block noisy boiler heating element...

Reviews: