Argo AT062310B Installation Procedure Download Page 1

5

insTALLATion procEdurE

Improper installation, adjustment, alteration, service or 

maintenance can cause injury or property damage.

Installation must conform to requirements of authority  

1. 

having jurisdiction or, in absence of such requirements, 

to Canadian Electrical Code, CSA C22.1 Part 1, and/or 

any local regulations in Canada, or National Electrical 

Code, ANSI/NFPA to (Latest Edition) and/or any local 

regulations and codes in the USA. Reference should 

also be made to local Electric utility regulations and 

other codes in effect in the area in which installation is 

to be made.

Where required by authority having jurisdiction, 

2. 

installation must conform to American Society of 

Mechanical Engineers Safety Code for Controls and 

Safety Devices for Automatically Fired Boilers, ANSI/

ASME No. CSD-1.

boiler is intended for indoor installation only and 

3. 

not subject to water spray or leakage.

!

  

CAUTION

Do not install boiler under potential water 

source.

(RULE OF THUMB: Water Under Wires.)

Electric Hydronic Block units are provided with 

4. 

mounting brackets for easy wall mounting. Use of 

lag screws or anchor bolts through holes provided, or 

on 3/4" plywood panel. On uneven walls, suggested 

mounting surface be provided such as two 2 x 4’s.

Surface of Electric Hydronic Block except back

5. 

 shall be 

mounted no closer than 20 inches to wall surface on 

left and 20 inches minimum to wall surface on right or 

more, depending on plumbing. Allow sufficient room 

from front of unit to door or wall to remove cover - at 

least 12 inches minimum.

20”

MIN

20”

MIN

10”

MIN

5’-3”

SUGGESTED

HEIGHT FOR

EASE OF

INSTALLATION

boIlER loCatIoN & ClEaRaNCE DImENSIoNS

NotE: 

greater clearances for access should supercede 

fire protection clearance.

Install unit with minimum clearance from top of unit to 

ceiling of 16 inches. If minimum requirements of space 

are used, suggested enclosure be exposed to means of 

ventilation. Electric Hydronic Block unit must be mounted 
level, using top of back plate as leveling point.

When installed in utility room, door should be wide 

6. 

enough to allow largest boiler part to enter, or to 

permit replacement of another appliance such as water 
heater.

Minimum clearances to combustible constructions 
are:

TOP ........................................................... 16 IN.

FRONT ...................................................... 12 IN.

LEFT SIDE................................................. 20 IN.

RIGHT SIDE .............................................. 20 IN.

REAR ........................................................... 0 IN.

BOTTOM....................................................10 IN.

Summary of Contents for AT062310B

Page 1: ...ting brackets for easy wall mounting Use of lag screws or anchor bolts through holes provided or on 3 4 plywood panel On uneven walls suggested mounting surface be provided such as two 2 x 4 s Surface...

Page 2: ...p supply may be located in this area below Circulator pump should be installed on supply side pumping away 6 Install gate valves at locations shown in Figures 2 3 so any boiler servicing requiring rem...

Page 3: ...7 primary secondary piping for Multiple zoning with ZONE VALVES primary secondary piping for Multiple zoning with circulators PRIMary secondary piping figure 2 figure 3...

Page 4: ...e ends before inserting into terminal block Tighten terminal screws Do not use pump rated greater than 5 amps Thermostat Connect thermostat or zone valve end switch to terminals TT and TT Figure 4 Do...

Page 5: ...re sizes specified conform to Canadian Electrical Code Canada or National Electric Code USA and include derating for ampacity and temperature Use copper wire only Check state and local requirements Re...

Page 6: ...or will continue to be energized for 3 minutes to purge boiler After 3 minutes control will de energize circulator Circ LED turns off If during start up or during operation safety end switch opens its...

Page 7: ...TACT SEC 120 VOLT WIRING POSE DES C BLES 120 VOLT 240 VOLT WIRING POSE DES C BLES 240 VOLT 120 VOLT FIELD WIRING POSE DES C BLES 120 VOLT SUR EN CHANTIER 240 VOLT FIELD WIRING POSE DES C BLES 240 VOLT...

Page 8: ...HERS SOURCE DU COURANT 120V 60HZ 1PH OU AUTRES OPTIONAL FLOW SWITCH BY OTHERS INTERRUPTEUR DE D BIT FACULTATIF OU AUTRES THERMOSTAT BY OTHERS THERMOSTAT OU AUTRES ELEMENT 1 L MENT No1 ELEMENT 1 RELAYS...

Page 9: ...T BLK BLANC NOIR WHT BLANC FUSE BLOCK BLOC DE FUSIBLE BLK NOIR L2 L1 POWER BLOCK BLOC DE PUISSANCE 240 VOLT FIELD WIRING POSE DES C BLES 240 VOLT EN CHANTIER EN CHANTIER 120 VOLT WIRING POSE DES C BLE...

Page 10: ...NOIR WHT BLANC RED ROUGE WIRE LEGEND L GENDE DES FILS DRY CONTACT WIRING POSE DES C BLES DE CONTACT SEC 120 VOLT WIRING POSE DES C BLES 120 VOLT 240 VOLT WIRING POSE DES C BLES 240 VOLT 120 VOLT FIELD...

Page 11: ...as the pressure remains less than 25 PSIG Hydronic block is now ready to be put into service Verify hydronic block circuit breaker or switch at service 1 entrance and depending on option hydronic blo...

Page 12: ...cluded with this manual Turn off hydronic unit circuit breaker at service en 1 trance and or disconnect switch Close gate valves near inlet and outlet of hydronic 2 block noisy boiler heating element...

Reviews: