DC Inverter Package R32 Cassette Type Unit
59
5.4.1.2 Work Procedure
Work shall be undertaken under a controlled procedure so as to minimize
the risk of a flammable gas or vapour being present while the work is being
performed.
5.4.1.3 General Work Area
All maintenance staff and others working in the local area shall be instructed
on the nature of work being carried out. Work in confined spaces shall be
avoided. The area around the workspace shall be sectioned off. Ensure that the
conditions within the area have been made safe by control of flammable material.
5.4.1.4 Checking for Presence of Refrigerant
The area shall be checked with an appropriate refrigerant detector prior to
and during work, to ensure the technician is aware of potentially flammable
atmospheres. Ensure that the leak detection equipment being used is suitable for
use with flammable refrigerants, i.e. non-sparking, adequately sealed or
intrinsically safe.
5.4.1.5 Presence of Fire Extinguisher
If any hot work is to be conducted on the refrigeration equipment or any
associated parts, appropriate fire extinguishing equipment shall be available to
hand. Have a dry powder or CO2 fire extinguisher adjacent to the charging area.
5.4.1.6 No Ignition Sources
No person carrying out work in relation to a refrigeration system which
involves exposing any pipe work that contains or has contained flammable
refrigerant shall use any sources of ignition in such a manner that it may lead to
the risk of fire or explosion. All possible ignition sources, including cigarette
smoking, should be kept sufficiently far away from the site of installation,
repairing, removing and disposal, during which flammable refrigerant can
possibly be released to the surrounding space. Prior to work taking place, the
area around the equipment is to be surveyed to make sure that there are no
flammable hazards or ignition risks. “No Smoking” signs shall be displayed.
Summary of Contents for AEG ECO 100PIH
Page 9: ...DC Inverter Package R32 Cassette Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Page 130: ...DC Inverter Package R32 Duct Type Unit 56 Only for AEG ECO 160PIH3 ...
Page 132: ...DC Inverter Package R32 Duct Type Unit 58 Only for AEG ECO 160PIH3 ...
Page 157: ...DC Inverter Package R32 Floor Ceiling Type Unit 5 2 Product Introduction 2 1 Overall Layout ...
Page 164: ...DC Inverter Package R32 Floor Ceiling Type Unit 12 100 140 A D E G B C 160 A C D E G B ...
Page 226: ...www argoclima com ...
Page 227: ... LUHG RQWUROOHU ZLWK ZHHNO WLPHU 8VHU DQG LQVWDOODWLRQ 0DQXDO ...
Page 233: ... LVSOD SSHDUDQFH LJXUH SSHDUDQFH RI ZLUHG FRQWUROOHU LUHG RQWUROOHU ...
Page 237: ... XWWRQV XWWRQ UDSKLFV LJXUH XWWRQ JUDSKLFV LUHG RQWUROOHU ...
Page 244: ... LUHG RQWUROOHU ...
Page 256: ... LJXUH 6WDWXV 9LHZ LUHG RQWUROOHU ...
Page 258: ... LJXUH XUUHQW UURU 9LHZ LUHG RQWUROOHU ...
Page 262: ... LUHG RQWUROOHU ...
Page 263: ... LUHG RQWUROOHU ...
Page 269: ... LJXUH ORFN VHWWLQJ LUHG RQWUROOHU ...
Page 275: ... ...
Page 287: ...www argoclima com ...