Duct Type Unit
37
⑩
. Wiring terminals should be connected firmly to the terminal board. Loose
connection is forbidden.
⑪
. After the electrical installation is finished, please use wire clamps to secure the
power cord, connection wire of indoor and outdoor units and the
communication cords. Make sure the wires are not clamped too tight.
⑫
. The wire gauge of power cord should be large enough. Damaged power cord
or other wires must be replaced by specialized wires. Wiring work must be
done according to national wiring rules and regulations.
2.3.2 Electrical Parameters
2.3.2.1 Wire Specifications and Fuse Capacity
Model
Power supply
Fuse
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
mm²
Indoor unit
220-240V ~50/60Hz
3.15
1.0
Model
Power supply
Circuit
breaker
capacity
Min. sectional
area of power
cord
V/Ph/Hz
A
mm
2
AEG ECO PLUS 35PIH
220-240V ~50/60Hz
16
1.5
AEG ECO PLUS 50PIH
16
1.5
AEG ECO PLUS 71PIH
20
2.5
AEG ECO PLUS 85PIH
20
2.5
AEG ECO PLUS 100PIH
32
4.0
32
4.0
AEG ECO PLUS 140PIH
AEG ECO PLUS 100PIH3
380-415V 3N~50/60Hz
16
1.5
16
1.5
AEG ECO PLUS 140PIH3
16
1.5
AEG ECO PLUS 160PIH3
NOTES:
①
. Fuse is located on the main board.