Duct Type Unit
33
2.2.7 Installation of the Duct
2.2.7.1 Dimensions of the Supply Air Outlet/Return Air Inlet
Supply Air Outlet
Return Air Inlet
Unit: mm
Item
Model
Supply Air Outlet
Return Air Inlet
A
B
C
D
ADG ECO PLUS 35PH
122
585
700
200
ADG ECO PLUS 50PH
122
885
1000
200
ADG ECO PLUS 71PH
215
740
871
234
ADG ECO PLUS 85PH
215
740
871
234
ADG ECO PLUS 100PH
215
1153
1188
220
ADG ECO PLUS 140PH
197
1151
1362
264
ADG ECO PLUS 160PH
197
1151
1362
264
2.2.7.2 Return Air Method
(1) The default ex-factory return air method is from the back. The return air
cover shall be installed at the bottom of the unit, as is shown in the
following figure.