Display colour change with parameters  

[r-cF]

, independent of OUT1.

Display colour change with parameter  

[G-cF]

, independent of OUT1.

Measured value between cFL and cFH;
Display = red

Measured value between cFL and cFH;
Display = green

Colour change display green

Colour change display red

1

Initial value of the measuring range

2

Final value of the measuring range

cFL

Lower limit value (independent of 

the output function)

cFH

Upper limit value (independent of 

the output function)

10 Operation

After power on, the unit is in the Run mode (= normal operating mode). It carries out its measurement and evaluation functions and provides output 
signals according to the set parameters.

Operation indication 

 7 Operating and display elements.

10.1 Read set parameters

► 

Press [

].

► 

Press [

] or [

] until the requested parameter is displayed.

► 

Briefly press [

].

> The unit displays the corresponding parameter value for approx. 30 s; then it changes to the process value display.

10.2 Self-diagnosis / error indications

The unit has many self-diagnostic options.

 › It monitors itself automatically during operation.
 › Warnings and faults are displayed (even if the display is deactivated), in addition they are available via the parameter setting software.

Display

Status LED

OUT1

Status LED

OUT2

Type of fault *)

Fault / warning

Corrective measures

none

F

Supply voltage too low.

 Check / correct the supply voltage.

SC

flashes

flashes

flashes

F

Excessive current at switching 

outputs OUT1 and OUT2 **).

► 

Check switching outputs for short-circuit or 

    excessive current; remove the fault.

SC1

flashes

flashes

F

Excessive current at switching outputOUT1 **).

► 

Check switching output  OUT1 for 

    short-circuit or excessive current; remove the fault.

SC2

flashes

flashes

F

Excessive current at switching output OUT2 **).

► 

Check switching output OUT2 

    for short-circuit or excessive current; 

    remove the fault.

Loc

W

Parameter setting locked via pushbuttons

► 

Unlock buttons 

 9.1 Parameter setting 

    in general

 →

“Locking / unlocking“.

C.Loc

W

Parameter setting locked via pushbuttons, 

parameter setting is active via IO-Link 

communication 

 9.1.

 Wait until parameter setting via IO-Link 

     is finished.

S.Loc

W

Setting buttons locked via parameter software. 

Parameter change is rejected 

 9.1.

 Unlocking only possible via

     IO-Link interface / parameter setting software.

OL

W

Process value too high

(measuring range exceeded).

 Check / reduce system pressure / select unit 

     with corresponding measuring range.

UL

W

Process value too low

(value below measuring range).

 Check / increase system pressure / select unit 

    with corresponding measuring range.

Err flashes

F

Internal fault / malfunction.

 Contact the manufacturer.

*) F = fault
    W = warning

**) The output remains deactivated as long as the excessive current / short circuit continues.

Summary of Contents for TSE3-D

Page 1: ...s of the warranty claims 1 Preliminary note 1 1 1 Symbols used 1 2 Safety instructions 1 3 Functions and features 2 3 1 Applications 2 4 Function 2 4 1 Communication parameter setting evaluation 2 4 2...

Page 2: ...tem pressure It generates output signals according to the operating mode and the parameter setting It moreover provides the process data via IO Link The unit is laid out for fully bidirectional commun...

Page 3: ...o indicated System pressure above AEP2 20 20 5 mA System pressure below ASP2 4 3 8 mA Fault indication according to Namur 21 5 mA 4 4 IO Link General information This unit has an IO Link communication...

Page 4: ...onnected only by using any Listed CYJV 7 or R C CYJV2 8 cord in respect of Condition of Acceptability having suitable ratings Core colours BK black BN brown BU blue WH white OUT1 switching output or I...

Page 5: ...pressure at which OUTx switches with hysteresis setting Prerequisite OUTx setting is Hno or Hnc FHx FLx Upper lower limit value for system pressure at which OUTx switches with window setting Prerequis...

Page 6: ...ur window in the coLr parameter r cF or G cF diS Update rate and orientation of the display 9 Parameter setting During parameter setting the unit remains in the operating mode It continues to monitor...

Page 7: ...isplayed During operation Loc is briefly displayed if you try to change parameter values For unlocking Make sure that the unit is in the normal operating mode Press imultaneously for 10 s uLoc is disp...

Page 8: ...ing function Hno hysteresis function NO Hnc hysteresis function NC Fno window function NO Fnc window function NC Select OU2 and set the analogue function Hno hysteresis function NO Hnc hysteresis func...

Page 9: ...ss and hold or until is displayed Briefly press 9 4 7 Reset all parameters to factory setting Select rES Press Press and hold or until is displayed Briefly press We recommend noting down your own sett...

Page 10: ...r change display red 1 Initial value of the measuring range 2 Final value of the measuring range Representation r 12 G 12 only possible when ou2 switching output Display colour change for the paramete...

Page 11: ...Display Status LED OUT1 Status LED OUT2 Type of fault Fault warning Corrective measures none F Supply voltage too low Check correct the supply voltage SC flashes flashes flashes F Excessive current at...

Page 12: ...11 2 Further technical data Further technical data and scale drawing at www argo hytos com 12 Factory setting Factory setting User setting SP1 25 MEW rP1 23 MEW ou1 Hno ou2 I SP2 75 MEW rP2 73 MEW ASP...

Reviews: