Table. 5.4.4 - 76. AR Status and basic settings.
Setting
Range
Default
Description
AR Mode
0: Disabled
1: Enabled
0:
Disabled Enables and disables the auto-recloser function in the configuration.
AR LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
1: On
Set mode of AR block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
AR LN
behaviour
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
Displays the mode of AR block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
Use AR
On/Off
signals
0: Yes
1: No
1: No
Selects whether or not the AR ON and AR OFF signals are used. If set to "No" the
auto-recloser is always in use. If set to "Yes" binary signal set to "AR ON/OFF" has to
be active for the auto-recloser to be enabled.
AR
Status
0: AR is
inhibit
1: AR is ready
2: AR is
locked
3: AR is
running
4: AR is not
running
5: Lock out
delay is
running
6: Reclaim
time counting
7: Start time
counting
8: Dead time
counting
9: Arcing or
discr. time
counting
10: Reclaim
time counting
11: AR1
Requested
12: AR2
Requested
13: AR3
Requested
14: AR4
Requested
15: AR5
Requested
16: Executing
Shot1
17: Executing
Shot2
18: Executing
Shot3
19: Executing
Shot4
20: Executing
Shot5
21: Shot
Clear
-
When clicked open, displays the status of the function.
A
AQ
Q-S255
-S255
Instruction manual
Version: 2.06
122
© Arcteq Relays Ltd
IM00025
Summary of Contents for AQ-S255
Page 1: ...AQ S255 Bay control IED Instruction manual ...
Page 2: ......