![Arcteq AQ-S255 Instruction Manual Download Page 30](http://html1.mh-extra.com/html/arcteq/aq-s255/aq-s255_instruction-manual_2964907030.webp)
Name
Unit
Range
Step
Description
ILx reactive current
("ILx Reactive Current
p.u.")
× In
-1250.00…1250.00 0.01
The reactive current component measurement (in p.u.)
from each of the phase current channels.
Positive sequence
resistive current
("Pos.Seq Resistive
Current p.u.")
× In
-1250.00…1250.00 0.01
The resistive current component measurement (in p.u.) from
the positive sequence current channel.
Positive sequence
reactive current
("Pos.Seq Reactive
Current p.u.")
× In
-1250.00…1250.00 0.01
The reactive current component measurement (in p.u.) from
the positive sequence current channel.
Residual resistive
current I0x
("I0x Residual Resistive
Current p.u.")
× In
-1250.00…1250.00 0.01
The resistive current component measurement (in p.u.) from
the residual current channel I0x.
Residual reactive
current I0x
("I0x Residual Reactive
Current p.u.")
× In
-1250.00…1250.00 0.01
The reactive current component measurement (in p.u.) from
the residual current channel I0x.
Table. 5.2.1 - 24. Primary phase current component measurements.
Name
Unit
Range
Step
Description
Primary resistive current
ILx
("ILx Resistive Current
Pri.")
A
-100000.00
…100000.00
0.01
The primary resistive current component measurement
from each of the phase current channels.
Primary reactive current
ILx
("ILx Reactive Current
Pri.")
A
-100000.00
…100000.00
0.01
The primary reactive current component measurement
from each of the phase current channels.
Primary positive sequence
resistive current
("Pos.Seq. Resistive
Current Pri.")
A
-100000.00
…100000.00
0.01
The primary resistive current component measurement from
the positive sequence current channel.
Primary positive sequence
reactive current
("Pos.Seq. Reactive
Current Pri.")
A
-100000.00
…100000.00
0.01
The primary reactive current component measurement from
the positive sequence current channel.
Primary residual resistive
current I0x
("I0x Residual Resistive
Current Pri.")
A
-100000.00
…100000.00
0.01
The primary resistive current component measurement from
both of the residual current channels.
Primary residual reactive
current I0x
("I0x Residual Reactive
Current Pri.")
A
-100000.00
…100000.00
0.01
The primary reactive current component measurement from
both of the residual current channels.
Table. 5.2.1 - 25. Secondary phase current component measurements.
Name
Unit
Range
Step
Description
Secondary resistive
current ILx
("ILx Resistive Current
Sec.")
A
-300.00…300.00 0.01
The secondary resistive current component measurement
from each of the phase current channels.
Secondary reactive
current ILx
("ILx Reactive Current
Sec.")
A
-300.00…300.00 0.01
The secondary reactive current component measurement
from each of the phase current channels.
A