Number of recordings
0…100, 60 MB of shared flash memory reserved
The maximum number of recordings according to the chosen signals and operation time setting
combined
9.3 Tests and environmental
Electrical environment compatibility
Table. 9.3 - 362. Disturbance tests.
All tests
CE-approved and tested according to EN 60255-26
Emissions
Conducted emissions:
EN 60255-26 Ch. 5.2, CISPR 22
150 kHz…30 MHz
Radiated emissions:
EN 60255-26 Ch. 5.1, CISPR 11
30…1 000 MHz
Immunity
Electrostatic discharge (ESD):
EN 60255-26, IEC 61000-4-2
Air discharge 15 kV
Contact discharge 8 kV
Electrical fast transients (EFT):
EN 60255-26, IEC 61000-4-4
Power supply input 4 kV, 5/50 ns, 5 kHz
Other inputs and outputs 4 kV, 5/50 ns, 5 kHz
Surge:
EN 60255-26, IEC 61000-4-5
Between wires 2 kV, 1.2/50 µs
Between wire and earth 4 kV, 1.2/50 µs
Radiated RF electromagnetic field:
EN 60255-26, IEC 61000-4-3
f = 80….1 000 MHz, 10 V/m
Conducted RF field:
EN 60255-26, IEC 61000-4-6
f = 150 kHz….80 MHz, 10 V (RMS)
Table. 9.3 - 363. Voltage tests.
Dielectric voltage test
EN 60255-27, IEC 60255-5, EN 60255-1
2 kV (AC), 50 Hz, 1 min
Impulse voltage test
EN 60255-27, IEC 60255-5
5 kV, 1.2/50 µs, 0.5 J
Physical environment compatibility
Table. 9.3 - 364. Mechanical tests.
Vibration test
EN 60255-1, EN 60255-27, IEC 60255-21-1 Class 1
2…13.2 Hz, ± 3.5 mm
13.2…100 Hz, ± 1.0 g
Shock and bump test
EN 60255-1,EN 60255-27, IEC 60255-21-2 Class 1
20 g, 1 000 bumps/direction.
A
AQ
Q-F215
-F215
Instruction manual
Version: 2.04
484