WEKA_IOM_VLI_EN / 17.03.2020
18 / 31
4. Put the float system back in the float chamber and fit the float stopper, see chapter 8.3.
5. Reinstall the visual level indicator on the tank.
Unsuitable screws, nuts and seals may result in leaks and cause damage and may endanger
people and the environment. Only use components suited to the application.
6. Recommission the visual level indicator, as described in point 10.
13.
Operating, transport and storage conditions
13.1 Operating
conditions
According to the type plate and order confirmation / drawing
Environment (standard):
-
Temperature:
-20°C to +60°C
-
Relative humidity:
10% to 95%
The operating and ambient conditions may be restricted for products for use in potentially
explosive atmospheres. Please comply with the information on the type plate and explosion-proof
plate.
13.2
Transport and storage conditions
-
Protect the visual level indicator from severe jolts.
-
Do not place heavy items on the visual level indicator or its packaging.
-
To avoid damage in transit, secure the flat with a safety device.
-
Store the visual level indicator in a dry environment.
-
Avoid contact with water and moisture
-
Temperature:
-40°C to +80°C
-
Relative humidity:
10% to 95%
14. Technical
data
General information can be gathered from the data sheet for the model in question.
Order-specific data as per type plate and order confirmation / drawing.
15.
Disassembly / disposal
15.1 Disassembly
Risk of burning! Working on hot visual level indicators may result in physical injuries and burns.
The surfaces of the standpipes and the process connections may become hot. Allow the tank to
cool to the ambient temperature before working on the visual level indicator. Wear suitable
protective equipment (gloves, face guard, possibly breathing apparatus). Keep a sufficient
distance away while the machine is in operation.
Visual level indicators run at excessive pressure carry pressure-related risks. Depressurise the
tank before working on the visual level indicator and observe the information of the local valid
pressure regulations, i.e. Pressure Equipment Directive 2014/68/EU.
Summary of Contents for 23013
Page 1: ...Installation and Operating Manual Visual Level Indicator VLI Date 17 03 2020 Version E 10 1...
Page 2: ...WEKA_IOM_VLI_EN 17 03 2020 1 31 Notes Order Date...
Page 23: ...WEKA_IOM_VLI_EN 17 03 2020 22 31 20 EU Declaration of Conformity for explosion proof devices...
Page 24: ...WEKA_IOM_VLI_EN 17 03 2020 23 31 21 ATEX Certificate Type Examination Certificate...
Page 25: ...WEKA_IOM_VLI_EN 17 03 2020 24 31...
Page 26: ...WEKA_IOM_VLI_EN 17 03 2020 25 31...
Page 27: ...WEKA_IOM_VLI_EN 17 03 2020 26 31 22 IECEx Certificate of Conformity CoC...
Page 28: ...WEKA_IOM_VLI_EN 17 03 2020 27 31...
Page 29: ...WEKA_IOM_VLI_EN 17 03 2020 28 31...