background image

 

 

 

WEKA_IOM_VLI_EN  /  17.03.2020 

13 / 31 

9. Installation 

Preparations for installing (point 8) the visual level indicator must be completed before installation.

 

 

  If the data marked on the type plate (density, max. operating pressure, max. operating 

temperature, connection dimensions, material, etc.), does not match the application, the visual 
level indicator may display an incorrect level, and it may be damaged and pose a risk to people 
and the environment. Make sure that the data marked on the type plate matches the application. 

  Unsuitable screws, nuts and seals may result in leaks and cause damage and may endanger 

people and the environment. Only use components suited to the application. 

  For visual level indicators with weld sockets as process connections, only suitable (approved) 

welding processes may be used. The same applies to the selection of filler materials. 

  Working on hot or pressurised visual level indicators may result in physical injuries, burns, 

chemical burns or poisoning. Depressurise the tank and allow it to cool to the ambient 
temperature before working on the visual level indicator. Wear suitable protective equipment 
(gloves, face guard, possibly breathing apparatus). 

   The visual level indicator may only be used for the purposes recorded on the type plate and the 

Ex label. 

  Falling parts (screws, floats, etc.) may create impact sparks and lead to an explosion in 

potentially explosive atmospheres. Make sure that there isn’t a potentially explosive atmosphere 
and that no parts are falling when working on the visual level indicator. 

  In the absence of equipotential bonding, static charges may build up, which may result in 

sparking and lead to explosions. To equalise the potential, permanently connect the metallic 
housing of the visual level indicator (float chamber) to the equipotential bonding conductor of the 
system (tank).  
Possible equipotential bonding connections: 

-

  Weld the weld sockets (process connection) to the tank 

-

  Connect the flanges (process connection) to the tank via at least two bolts.  

-

  If none of these are possible, set up an equipotential bonding conductor of at least 4mm² 

via a clamp connection. 

-

  The connection points must be free of paint. 

Also, the accessories, like magnet switches, transmitters, etc. must be connected to the potential 
equalisation system. 

 

 

Summary of Contents for 23013

Page 1: ...Installation and Operating Manual Visual Level Indicator VLI Date 17 03 2020 Version E 10 1...

Page 2: ...WEKA_IOM_VLI_EN 17 03 2020 1 31 Notes Order Date...

Page 3: ...2 Cleaning visual level indicator 16 12 1 Cleaning the outside 16 12 2 Cleaning the float chamber and the float 16 12 3 Cleaning the float chamber and float for a top of tank assembly 17 13 Operating...

Page 4: ...1 HighPressure Power 250 26431 HighPressure Power 315 38400 HighPressure Power 400 38500 HighPressure Power 500 39020 PetroLine 20 39021 PetroLine 20 low density 39050 PetroLine 50 39051 PetroLine 50...

Page 5: ...re Equipment Directive 2014 68 EU When opening the visual level indicator bear in mind that the fluids and gases it contains could be hazardous to health It is imperative that you comply with the safe...

Page 6: ...for fluids The visual level indicator may only be used for the purposes recorded on the type plate The information noted down on the type plate and data sheet must conform with ideal plant operating...

Page 7: ...standpipe 6 Float 7 Indication rail see below for details 8 Type plate with customer specific parameters 9 Top sticker 10 Service connections top and bottom Process and service connections may be Fla...

Page 8: ...cess connections top and bottom 31 Top service flange plug 32 Possible ventilation hole with plug 33 Bottom service flange plug 34 Possible drain hole with plug 5 2 Top of tank design Figure 4 2 40 Fl...

Page 9: ...ription The fluid level in the float chamber corresponds to the fluid level in the tank communicating vessels The bar magnet has been integrated into the float in a way that means the centre of the ba...

Page 10: ...for assembly 8 1 Unpacking 1 Lay the visual level indicator and the packaging flat on the floor 2 Remove the packing tape 3 Remove the staples in the overlapping cardboard at both ends of the packagi...

Page 11: ...he functioning of the visual level indicator Remove them completely An incorrectly installed float will lead to the incorrect fill level being displayed Slide the float into the float chamber as shown...

Page 12: ...e bottom service flange plug If you re dealing with a flange tighten the screws diagonally Bear any tightening torque information in mind VLI line VLI type Torque Nm SmartLine 34000 20 34110 StandarLl...

Page 13: ...float is in the float chamber and is stopped from moving around thanks to a screw at the bottom end of the chamber 3 Type 23013 Remove cable tie and dispose properly Type 25270 Turn the screw until th...

Page 14: ...mperature before working on the visual level indicator Wear suitable protective equipment gloves face guard possibly breathing apparatus The visual level indicator may only be used for the purposes re...

Page 15: ...nections The visual level indicator must be installed in a vertical position You can check this with a spirit level on the float chamber Deviations of up to 5 from the vertical position are acceptable...

Page 16: ...cator if it is working properly Do not use an unsealed visual level indicator Working on hot or pressurised visual level indicators may result in physical injuries burns chemical burns or poisoning De...

Page 17: ...ure carry pressure related risks Depressurise the tank before working on the visual level indicator and observe the information of the local valid pressure regulations i e Pressure Equipment Directive...

Page 18: ...ear suitable protective equipment gloves face guard possibly breathing apparatus Keep a sufficient distance away while the machine is in operation Visual level indicators run at excessive pressure car...

Page 19: ...al level indicator or its packaging To avoid damage in transit secure the flat with a safety device Store the visual level indicator in a dry environment Avoid contact with water and moisture Temperat...

Page 20: ...ack the float in separate packaging 15 2 Disposing of the visual level indicator Protect the environment and take the visual level indicator to be disposed of properly 16 Troubleshooting Problem Possi...

Page 21: ...cessary 17 Label 17 1 Type plate The visual level indicator may only be used for the purposes recorded on the type plate The information noted down on the type plate and data sheet must conform with i...

Page 22: ...WEKA_IOM_VLI_EN 17 03 2020 21 31 19 EU Declaration of Conformity for non explosion proof devices...

Page 23: ...WEKA_IOM_VLI_EN 17 03 2020 22 31 20 EU Declaration of Conformity for explosion proof devices...

Page 24: ...WEKA_IOM_VLI_EN 17 03 2020 23 31 21 ATEX Certificate Type Examination Certificate...

Page 25: ...WEKA_IOM_VLI_EN 17 03 2020 24 31...

Page 26: ...WEKA_IOM_VLI_EN 17 03 2020 25 31...

Page 27: ...WEKA_IOM_VLI_EN 17 03 2020 26 31 22 IECEx Certificate of Conformity CoC...

Page 28: ...WEKA_IOM_VLI_EN 17 03 2020 27 31...

Page 29: ...WEKA_IOM_VLI_EN 17 03 2020 28 31...

Page 30: ...WEKA_IOM_VLI_EN 17 03 2020 29 31...

Page 31: ...WEKA_IOM_VLI_EN 17 03 2020 30 31...

Reviews: