Arada Farringdon
Page 18
OPERATING INSTRUCTIONS
IMPORTANT
INFORMATION
Important notes on usage to meet the
requirements of Smoke Control exemption -
Always recharge onto hot embers.
After re-charging, leave the door ajar
for approximately 3 minutes to
establish good combustion.
Do not leave the appliance unattended
until flames are well established.
Periodic burning out of the fuel bed at
high output to combust any remaining
charcoal.
NOTE :
The minimum air control setting is governed
in manufacture to meet the requirements of
Smoke Control exemption and as a result
the appliance will NOT shut down
completely when in the minimum air
position setting.
Refuelling on to a low fire bed
If there is insufficient burning material in the fire bed
to light a new fuel charge, excessive smoke
emission can occur. Refuelling must be carried out
onto a sufficient quantity of glowing embers and
ash that the new fuel charge will ignite in a
reasonable period. If there are too few embers in
the fire bed, add suitable kindling to prevent
excessive smoke.
Fuel overloading
The maximum amount of fuel specified in this
manual should not be exceeded, overloading can
cause excess smoke.
Operation with door left open
Operation with the door open can cause excess
smoke. The appliance must not be operated with
the appliance door left open except as directed in
the instructions.
Dampers left open
Operation with the air controls or dampers open
can cause excess smoke. The appliance must not
be operated with air controls or dampers door left
open except as directed in the instructions.
Summary of Contents for Farringdon 8
Page 27: ...Page 27 Arada Farringdon...