1100-2184 Rev 0
28
3.12 Method 2: Set Modbus ID Manually
Modbus IDs can be manually assigned to the AT-G-ALERT devices prior to wiring.
Wire a single AT-G-ALERT Modbus port to the controller’s Modbus terminal block. It is
recommended to use the EZ-wire kit available with the AT-G-ALERT-C controller for ease.
1. From
Settings
, open the
Set Modbus ID
screen to select and apply a specific
Modbus ID.
2. Tap
Search
to connect to the device. If the unit does not have factory Modbus ID #1,
this can be restored by doing a factory reset.
In case the AT-G-ALERT has had its Modbus ID changed to some ID other than the
default address 1, do the following to reset to factory settings:
a. Power OFF the AT-G-ALERT. Set dipswitch-8 to the ON position.
b. Power ON the AT-G-ALERT (buzzer should sound). Reset dipswitch-8 to the
OFF position (buzzer should turn off).
Figure 30 - Set Modus ID
Summary of Contents for AquiTron AT-G-ALERT-C
Page 1: ...1100 2184 Rev 0 1...