Dispersant Configuration
On the main screen, press NEXT. Now touch the Dispersant parameter box. The Dispersant
screen will appear to allow users to set dispersant settings. (Pictures 22 and 23)
Picture 22. Dispersant parameter box.
Picture 23. Dispersant screen
Setting values include MODE (including Disabled, Flow, Continuous, ORP, Bleed, and Inhibitor),
PUMP SIZE, DOSE RATE and OUTPUT. Press each parameter to input a value or choose pre-
determined options. (Picture 23)
Period: Increasing the period, allows lower chemical dose rates to be achieved from a large
pump. The default period is 1min, which means that the controller regulates the pump to get the
dose rate for each minute. When it is set to 10min, the controller regulates the pump every
10minutes. This allows lower dosing rates from large pumps and doses more accurately. Period
is automatically adjusted when pump size and dose rates are selected.